GX9 ASD Installation and Operation Manual 73
Figure 32. Complete the Virtual Linear Pump Setup.
Figure 33. Run the Motor/Pump in the Direct Mode.
16. Press the Stop key to complete
the setup.
17. Click Exit to save settings
(Exit becomes available at
zero Hz).
18. Press the ESC key until
reaching the Frequency
Command screen.
19. From the Frequency Com-
mand screen press ESC, scroll
to the Control field, and select
Direct Mode if using no feed-
back (if using feedback go to
Step 22. on pg. 74).
20. While in the Local mode, press
Run.
21. While running, adjust parame-
ters F500 and F501 to stabilize
operation if unstable.
Press ESC