–40–
Installation Manual
EN
13.LC Easy monitor
The various sensor temperatures of the indoor unit and outdoor unit of light commercial models and operating
conditions can be checked together.
The following items can be checked.
*1: “Refrigerant amount check” shows one of the following.
For details on the various content, refer to the Installation Manual and Service manual of the outdoor unit.
“No refrigerant leak detected”
“Possible refrigerant leak”
“Initializing/Undeterminable (see manual)”
“Preliminarily OK. Still processing.”
“Undeterminable (see manual)
“On process”
NOTE
Cannot be used except with light commercial models. “No function” is displayed.
Even with light commercial models, some items may not display their data.
If this happens, the data in that item appears as “--”. For details on items and the content they display, refer to the Installation
Manual and Service manual of the indoor unit and outdoor unit.
“LC Easy monitor” display temperature values in same unit as selected in “Set temp. unit” (“°C” or “°F”).
1 In the “Field setting menu” screen, press
[ ] and [ ] to select “LC Easy monitor”,
and then press [ Set/Fix]
Press [ ] and [ ] to be able to switch the
screen display.
In a group connection, after a selection in the unit
selection screen, move to the “LC Easy monitor”
screen.
2 After checking, press [ Return]
Return to the “Field setting menu” screen.
Indoor unit / remote controller
relationship
Unit Outdoor unit relationship Unit
Remote sensor °F Outdoor heat exchange temperature (TE) °F
Return air temperature (TA) °F Outdoor temperature (TO) °F
Indoor heat exchange temperature (TCJ) °F Compressor discharge temperature (TD) °F
Indoor heat exchange temperature (TC) °F Compressor suction temperature (TS) °F
Discharge temperature (TF) °F
Outdoor unit heat exchange temperature
(TL)
°F
Fan(IDU) speed rpm Current(ODU) A
Fan(IDU) operating h Comp. speed rps
Filter usage h Comp. operation h
Fan1(ODU) speed rpm
Fan2(ODU) speed rpm
Refrigerant amount check *1
High pressure (Pd) MPa
Low pressure (Ps) MPa

Other manuals for Toshiba RBC-AWSU52-UL