RT-SVP011E-EN 103
Troubleshooting
VFD Supply Fan Motor
Current Overload – X
where X is “1” or “2”
Unit Warning Latching*
Supply fan X VFD indicates peak current of
approximately 200% of rated current was exceeded
for 1.5 seconds.
This is a drive enforced lockout.
Failure of fan X with the other fan available:
Generate a “Supply Fan X Proving Failure” diagnostic
on the failed fan, allow the working fan to continue
and lock-out all heating operation.
Failure of fan X with the other fan not-available:
Generate a “Supply Fan X Proving Failure” diagnostic
on the failed fan and shutdown the unit.
*The Latching behavior for this diagnostic is latched
in the drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio™ 800
controller be cleared in the Symbio™ 800 controller
by setting its persistence to Non-Latching.
This drive alarm may be Trip Locked at the TR150
d
rive. If the drive determines that the condition could
cause damage the drive protects itself by generating
a Trip Lock that can only be cleared by cycling power.
Local
VFD Supply Fan Short
Ci
rcuit – X
where X is “1” or “2”
Unit Warning Latching*
Supply fan X VFD indicates a short circuit in the motor
windings or the motor terminals was detected. Fan
operation is not recommended until the short circuit
is removed.
Failure of fan X with the other fan available:
Generate a “Supply Fan X Proving Failure” diagnostic
on t
he failed fan, allow the working fan to continue
and lock-out all heating operation.
Failure of fan X with the other fan not-available:
Generate a “Supply Fan X Proving Failure” diagnostic
on the failed fan and shutdown the unit.
* The Latching behavior for this diagnostic is latched
in the drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio™ 800
controller by setting its persistence to Non-Latching.
This drive alarm may be Trip Locked at the TR150
d
rive. If the drive determines that the condition could
cause damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by
cycling power.
Local
VFD Torque Limit
Exceeded– Cprsr1A
Circuit
Immediate
Shutdown
Latching*
Supply fan X VFD indicates motor torque is higher
than expected.
* The Latching behavior for this diagnostic is latched
in the drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio™ 800
controller by setting its persistence to Non-Latching.
The behavior for this diagnostic is set to non-latching
in the
drive and will be cleared when the condition is
no longer active.
Local
Diagnostics Target Severity Persistence Condition / Response Reset Level