RT-SVP011E-EN 55
TD7 Display
Arbitration Method
Allows selection of the active source of setpoints and settings:
Full Source – Result of arbitration from externa
l controls (For example: Tracer
®
SC+, TGP2,
3
rd
party system control).
Local Source – Isolates unit setpoints, settings, and sensors to local wired or wireless
sources. Removes Full
Sources.
Default Source – Isolates un
it to TD7 Display setpoints and settings, and local sensors.
Removes Local Source and Full Sources.
Feature Settings
Features Settings allows you to enable or disable features and functions.
Table 19. Feature settings value
Value Range (default) Description
Economizer Airside Enable Default
Auto (Disable, Enable,
Auto)
Aut
o, the controller uses sensor values and setpoints to
enable an
d disable economizer operation. Enable,
economizer operate as first stage of cooling. Disable,
disables economizer operation.
Economizer Control Fallback
Reference Enthalpy (Dry
Bu
lb, R
eference Enthalpy,
Comparative Enthalpy)
When Economizer with Comparative Enthalpy is
configured, control will fall back to Reference Enthalpy
in the event of a failure.
Balanced Compressor Staging Disable (Disable, Enable) Disabled by default.
Traq Enable Enable (Disable, Enable) Enabled when unit is configured for Traq.
Outdoor Air Flow Compensation
Enable
En
able (Disable, Enable) Enabled when variable speed fan configured.
Demand Control Ventilation
Enable
En
able (Disable, Enable) Enabled when configured.
Pre Cool Enable Command Enable (Disable, Enable) Enabled by default.
Morning Warmup Enable
Command
Enabl
e (Disable, Enable) Enabled when heat configured.
Daytime Warmup Enable
Command
Enabl
e (Disable, Enable) Enabled when heat configured.
Dehumdification Enable
Command
Enabl
e (Disable, Enable) Enabled when reheat is configured.
Occupied Dehumidific
ation Enable Enable
(Disable, Enable) Enabled when reheat is configured.
Unoccupied Dehumidification
Enable
En
able (Disable, Enable) Enabled when reheat is configured.
Unoccupied Cooling Mechanical
Enable
En
able (Disable, Enable) Enabled by default.
Unoccupied Cooling Economizing
Enable
En
able (Disable, Enable) Enabled by default.
Unoccupied Heating Enable Enable (Disable, Enable) Enabled when heat configured.
Loss of Charge Detection Enable (Disable, Enable) Enabled by default.
Hot Gas Bypass Enable (Disable, Enable) When configured.
Condenser Reheat Enable Enable (Disable, Enable) When
hot gas reheat is configured.
Supply Air Tempering Enable Disable (Disable, Enable) When Rapid Restart is configured.
Rapid Restart Enable Enable (Disable, Enable) When Rapid Restart is configured.
Rapid Restart Economizer Enable Enable (Disable, Enable) When Rapid Restart is configured.
Occupancy Input Wireless Enable Enable (Disable, Enable) Enabled by default when wireless is installed.