56 RT-SVP011E-EN
TD7 Display
Discharge Air Reset
This button allows edits to Discharge Air Cooling Reset and Discharge Air Heating Rest functions.
Settings are provided in table below.
Timed Override Request Wireless
Enable
Enable (Disable, Enable) Enabled by default when wireless is installed.
System Mode Wireless Enable Enable (Disable, Enable) Enabled by default when wireless is installed.
Space Temp Cooling Setpoint
Wireless Enable
En
able (Disable, Enable) Enabled by default when wireless is installed.
Space Temp Heating Setpoint
Wireless Enable
En
able (Disable, Enable) Enabled by default when wireless is installed.
Supply Fan Config Cmd Wireless
Enable
En
able (Disable, Enable) Enabled by default when wireless is installed.
Space Temperature Wireless
Enable
En
able (Disable, Enable) Enabled by default when wireless is installed.
Space Humidity Wireless Enable Enable (Disable, Enable) Enabled by default when wireless is installed.
Space Static Pressure Wireless
Enable
En
able (Disable, Enable) Enabled by default when wireless is installed.
Space CO
2
Concentration
Wireless Enable
Disable (Disable, Enable) Disabled by default when wireless is installed.
Superheat High Limit Lockout
Enable
En
able (Disable, Enable) Enabled by default.
Table 19. Feature settings value (continued)
Value Range (default) Description
Table 20. Discharge air reset value
Value Range (default) Description
Discharge Air Cooling Reset
None (None, Outdoor
Air, Zo
ne)
Selects the type of Discharge Air Cooling Reset to be
performed by controller. None, disables the function.
Outdoor Air Cooling Reset Start 90.0°F (71.0 - 95.0)
Starting outdoor air temperature at which discharge air
cooling setpoint will be
gin reset.
Outdoor Air Cooling Reset End 70.0°F (0 - 89.0)
Ending outdoor air temperature at which discharge air
cooling setpoint will r
eset.
Outdoor Air Cooling Reset Amount
Max.
5.0°F (0 - 20.0)
The amount the discharge air cooling setpoint will increase
over
the specified range.
Zone Cooling Reset Start Temp. 72.0°F (70.0 - 90.0)
Starting space temperature at which discharge air cooling
setpoint wi
ll begin reset.
Zone Cooling Reset End Temp. 69.0°F (50.0 - 71.0)
Ending space temperature at which discharge air cooling
setpoint wi
ll reset.
Zone Cooling Reset Amount Max 5.0°F (0 - 20.0)
The amount the discharge air cooling setpoint will increase
over
the specified range.
Discharge Air Heating Reset
None (None, Outdoor
Air, Zo
ne)
Selects the type of Discharge Air Heating Reset to be
performed by controller. None, disables the function.
Outdoor Air Heating Reset Start 32.0°F (0 - 59.0)
Starting outdoor air temperature at which discharge air
Heating
setpoint will begin reset.
Outdoor Air Heating Reset End 60.0°F (33.0 - 95.0)
Ending outdoor air temperature at which discharge air
Heating
setpoint will reset.
Outdoor Air Heating Reset
Amount Max.
5.0 °F (0 - 20.0)
The amou
nt the discharge air Heating setpoint will decrease
over the specified range.
Zone Heating Reset Start Temp. 69.0°F (50.0 - 71.0)
Starting space temperature at which discharg
e air Heating
setpoint will begin reset.
Zone Heating Reset End Temp. 72.0°F (70.0 - 90.0)
Ending space temperature at which discharge air Heating
setpoint wi
ll reset.