RT-SVP011E-EN 47
TD7 Display
Service Settings
Provides access to low level parameters required for all unit functionality.
Table 17. Service settings
Value Factory Default (Range) Description
Power-Up Start Delay 0 Sec (0-300)
Used to delay unit operation after a
power cycle
or after the termination of
all VOM/EOM events.
VAV Box Stroke Time 6 Min (1-10)
Used to manage unit airflow with VAV
system delays.
Duct
Static Press High Limit Setpoint 4.00 IWC (1.20-5.70)
Inhibits supply fan if duct pressure
exceeds
this setpoint.
Low Ambient Lockout Setpoint Configuration Dependent
Inhibits compressor operation if
outdoor air te
mperature drops below
this value.
Duct Static Press High Limit Protection Enable (Disable, Enable)
Disable this protection during active
supply
fan bypass mode. Always
enabled in non-bypass mode.
Design Air Flow Configuration Dependent Contact Trane Technical Support.
Local Atmospheric Pressure 14.7 PSIA (10-16)
This entry should reflect the average
pressur
e expected at the unit's
geographical elevation.
Relief Fan Maximum Speed Setpoint 200 RPM (100-5000)
This speed entry should reflect the
maximum
design relief airflow for the
given application.
Supply Fan Bypass Mode Enabled Off (Off, On)
Used to place the unit's supply fan
VFD(s) into
bypass mode.
Bypass Duct Static Diff. Pressure 0.3 IWC (0.3-2.0) Contact Trane Technical Support.
Occupied Bypass Time 120 Min (0-240)
The amount of time that will expire
before a unit
will return to unoccupied
mode after entering bypass.
Occupied Offset 1.5 °F (1-30)
This entry establishes a deadband
between occup
ied space heating and
space cooling setpoints.
Occupied Standby Offset 7.5 °F (1-30)
This entry establishes a deadband
between occup
ied standby space
heating and space cooling setpoints.
Cooling Design Delta Temp 20 °F (5.0-40.0) Contact Trane Technical Support.
Temp. Control Softload Time Cooling 120 Sec (0-1800) Contact Trane Technical Support.
Duct Static Pressure Softload Time 30 Sec (0-1800) Contact Trane Technical Support.
Occupied Dehumidification Offset 10.0% (5.0-15.0)
Occupied dehumidification terminates
when space
humidity falls below
occupied dehumid setpoint minus this
value.
Unoccupied Dehumidification Offset 10.0% (5.0-15.0)
Unoccupied dehumidification
t
ermina
tes when space humidity falls
below unoccupied dehumid setpoint
minus this value.
Purge Reheat Coil Interval Setting 120 Min (60-480) Contact Trane Technical Support.
Temp Control Softloading Time Heating 120 Sec (0-1800) Contact Trane Technical Support.
Occupied Space Cool Air Flow Cmd
Co
mpensatio
n
0.0% (-20.0-100.0) Contact Trane Technical Support.
Suction Superheat Setpoint 12.6 °F (9.0-27.0) Contact Trane Technical Support.
Suction Superheat Tracking Time 20.0 Sec (0.0-200.0) Contact Trane Technical Support.