46 RT-SVP011E-EN
TD7 Display
Econ Enable Min. Outdoor Air
Temp Setpoint
75°F (50.0 - 140.0)
Related to the economizer enable decision, this
default value determines th
e outdoor air
temperature below which economizing is enabled.
Outdoor Air Min. Flow
Setpoint Defau
lt
2199 cfm (0 - 60000.0)
Default requested minimum outdoor air flow
setpoint.
Relief Enable Position
Setpoint
25.0 (0 –
100)
Default setpoint to enable relief/exhaust fan
operation, based on outdoor air damper position.
Space Static Pressure
Setpoint Defau
lt
0.08 (-0.2 – 3.0) Space static pressure setpoint default value.
Design Min. OA Damper
Position
Setpoint Min Fan
25.0 (21.0 – 100.0)
(a)
Outdoor air flow compensation setpoint that
specifies the outdoor air damper position when
supply fan is at minimum speed.
Design Min. OA Damper
Position
Setpoint Mid Fan
20.0 (16.0 – 24.0)
(a)
Outdoor air flow compensation setpoint that
specifies the outdoor air damper position when
supply fan is at mid-point of speed range.
Design Min. OA Damper
Position
Setpoint Max Fan
15.0 (0.0 – 19.0)
(a)
Outdoor air flow compensation setpoint that
specifies the outdoor air damper position when
supply fan is at maximum speed.
DCV Min. Outdoor Air Damper
Position
at Min Fan
15.0 (15.0 – 100)
(a)
Outdoor air flow compensation with DCV, damper
position setpoint when supply fan at minimum
speed and space CO
2
at DCV setpoint (low limit).
DCV Min. Outdoor Air Damper
Positi
on at Max Fan
5.0 (0 – 5.0)
(a)
Outdoor air flow compensation with DCV, damper
position setpoint when supply fan at maximum
speed and space CO
2
at DCV setpoint (low limit).
Design Min. Outdoor Air Flow
Setpoint
6000.0 (2998.0
– 60000.0)
(a)
Outdoor air flow control (Traq) with DCV, air flow
setpoint when space at Design CO
2
Setpoint (high
limit).
DCV Min. Outdoor Air Flow
Setpoint
2000.0 (0 – 5002.0)
(a)
Outdoor air flow control (Traq) with DCV, air flow
setpoint when space at DCV CO
2
Setpoint (low
limit).
Design CO
2
Setpoint 1000.0 ppm (500.0 - 2000.0) Space design CO
2
high limit setpoint.
Design Min. OA Damper
Position
Setpoint
15.0% (15.0 - 100.0)
Outdoor air minimum position
cont
rol with DCV,
damper position setpoint when space at design CO
2
setpoint (high limit).
DCV Min. Outdoor Air Damper
Position
Setpoint
5.0% (0 - 5.0)
Outdoor air minimum position cont
rol with DCV,
damper position setpoint when space at DCV CO
2
setpoint (low limit).
DCV CO
2
Setpoint 400.0 ppm (50.0 - 900.0)
Space Demand Control Ventilation CO
2
low limit
setpoint.
Demand Limit Setpoint
Default
100.0% (0 - 100.0)
Demand
limit setpoint default value. This value is
normally
provided by the BMS to demand limit the
unit.
Cooling Capacity Enable
Default
100.0% (0 - 100.0)
Cooling cap
acity enable default value.
This value is
normally provided by the BMS to demand limit the
cooling capacity.
Heat Primary Enable Default 100.0% (0 - 100.0)
Heat primary capacity enable default value. This
value
is normally provided by the BMS to demand
limit the heating capacity.
Evap Leaving Air Temp
Setpoint Defau
lt
50.0°F (40.0 - 55.0)
Dehumidification modes of operation, evaporator
leaving air temperature setpoint.
Manual Overrides Timer
Setpoint
1 Hr (
1 - 78)
Sets the amount of time Manual Overrides are
allo
wed to
be active. Timer resets when an override
is applied.
(a) Ranges are dynamically calculated based on the other setpoint ranges.
Table 16. Unit settings value (continued)
Value Default (range) Description