RT-SVP011E-EN 45
TD7 Display
Unit Settings
Unit Settings are the basic parameters for unit operation and provide the default values for
setpoints and unit operating modes.
Table 16. Unit settings value
Value Default (range) Description
Arbitration Method
Full Source (Full Source, Local
Source, D
efault Source)
Full source-Result of arbitration from external
controls
(For example: Tracer
®
SC+, TGP2, 3rd
party system control).
Local source-Isolates unit setpoints, settings, and
sensors to l
ocal wired or wireless sources. Removes
Full Sources.
Default Source-Isolates unit to TD7 Display
se
tpoints
and settings, and local sensors. Removes
Local Source and Full Sources.
Supply Fan Configuration
Cmd Default
Co
ntinuous (Cycling, Continuous) Supply fan configuration.
Heat Cool Mode Request
Default (Single
zone units)
Auto (Heat, Cool, Off, Auto)
Default Heat Cool Mode Input for Single Zone VAV
and Constant Volume Zone Temperature units.
Heat Cool Mode Request
Default (Multi
zone units)
Heat (Heat, Cool, Off)
Default Heat Cool Mode Input for Multi Zone VAV
and Constant V
olume Discharge Air Temperature
units.
Discharge Air Cooling
Setpoint Defau
lt
55.0°F (40.0 - 75.0) Discharge air cooling setpoint.
Discharge Air Heating
Setpoint Defau
lt
100.0°F (50.0 - 120.0) Discharge air heating setpoint.
Duct Static Pressure Setpoint
Default
2.00 IWC (0.05 - 5.10) Duct static
pressure setpoint default.
Occupied Cooling Setpoint
Default
74.0°F (40.0 - 115.0) Space t
emperature occupied cooling setpoint.
Occupied Heating Setpoint
Default
71.0°F (40.0 - 115.0) Spa
ce temperature occupied heating setpoint.
Space Dehumidification
Setpoint Defau
lt
60.0% (40.0 - 65.0)
Space dehumidification enable setpoint in occupied
modes.
Unoccupied Cooling Setpoint 85.0°F (40.0 - 115.0) Space temperature unoccupied cooling setpoint.
Unoccupied Heating Setpoint 60.0°F (40.0 - 115.0) Space temperature unoccupied heating setpoint.
Space dehumidification
Unoccupied
Setpoint Default
60.0% (40.0 - 65.0)
Space dehumidification enable setpoint in
unoccupied mode.
Pre cool Setpoint 74.0°F (40.0 - 83.0)
Defines the space temperature above which pre-
cool wi
ll be exercised, when enabled.
Morning Warmup Setpoint 72.0°F (50.0 - 90.0)
Defines the space temperature below which
morning wa
rmup will be exercised, when enabled.
Daytime Warmup Setpoint 72.0°F (50.0 - 90.0)
Space temperature below which daytime warmup
will be enabled.
Occu
pied Standby Cooling
Setpoint Defau
lt
78.0°F (40.0 - 115.0)
Space temperature occupied standby cooling
setpoint.
Occupied Standby Heating
Setpoint Defau
lt
67.0°F (40.0 - 115.0)
Space temperature occupied standby heating
setpoint.
Occupancy Input Default Occupied (Occupied, Unoccupied) Occupancy input default value.
Economizer Min. Position
Setpoint Defau
lt
25.0% (0.0 - 100.0) Economizer damper minimum position setpoint.
Reference Enthalpy Setpoint 25.0 BTU/lbm (19.0 - 36.0)
Related to the economizer enable decision, this
default
value determines th
e outdoor air enthalpy
below which economizing is enabled.