48 RT-SVP011E-EN
TD7 Display
Suction Temp. Filter Base Time
Constant
0.0 Sec (0.0-20.0) Contact Trane Technical Support.
EXV Control Compressor Press Ratio
Min
1.500 (1.200-1.700) Contact Trane Technical Support.
EXV Control Pre-Position Hold Time 4.0 Sec (0.0-60.0) Contact Trane Technical Support.
EXV Control Pre-Position Setpoint 90.0% (50.0-300.0) Contact Trane Technical Support.
EXV Differential Pressure Estimate Min 40.00 PSID (29.01-72.52) Contact Trane Technical Support.
EXV Feedforward Evap. Approach
Te
mp.
Ba se
9.0 °F (0.0-27.0) Contact Trane Technical Support.
Ref Loss Suction Discharge Percent
Ckt1
2.0% (0.0-10.0) Contact Trane Technical Support.
Reference Loss Condenser Percent
Ckt1
5.0% (0.0-10.0) Contact Trane Technical Support.
Reference Loss Distributor Percent
Ckt1
15.0% (0.0-25.0) Contact Trane Technical Support.
Reference Loss Evaporator Percent
Ckt1
1.0% (0.0-10.0) Contact Trane Technical Support.
Reference Loss Subcooler Percent Ckt1 3.0% (0.0-10.0) Contact Trane Technical Support.
Ref Loss Suction Discharge Percent
Ckt2
2.0% (0.0-10.0) Contact Trane Technical Support.
Reference Loss Condenser Percent
Ckt2
5.0% (0.0-10.0) Contact Trane Technical Support.
Reference Loss Distributor Percent
Ckt2
15.0% (0.0-25.0) Contact Trane Technical Support.
Reference Loss Evaporator Percent
Ckt2
1.0% (0.0-10.0) Contact Trane Technical Support.
Reference Loss Subcooler Percent Ckt2 3.0% (0.0-10.0) Contact Trane Technical Support.
Condenser Reheat Softload Time 120 Sec (0-1800) Contact Trane Technical Support.
Condenser Reheat Staging Deadband 20.000 (10.000-100.000) Contact Trane Technical Support.
Cond Fan Control Reheat Diff Press
Se
tpoint
250.00 PSID (
85.00-300.00) Contact Trane Technical Support.
Cond Fan Control Cool Diff Press
Setpoint
90.00 PSID (
85.00-150.00) Contact Trane Technical Support.
Cond Fan Control Cool Diff Press Offset 15.00 PSID (5.00-25.00) Contact Trane Technical Support.
Cond Fan Control Cool Press Ratio
Setpoint
1.55 (1.500-2.500) Co
ntact Trane Technical Support.
Condenser Fan Air Coil Correction 11.880 (0.000-100.000) Contact Trane Technical Support.
Cond Fan Control Efficiency Check
Point
105.0 °F (95.0-115.0) C
ontact Trane Technical Support.
Purge Condenser Coil Interval Setting 90 Min (60-120) Contact Trane Technical Support.
Rapid Restart Complete Temp Setting 74.0 °F (65.0-85.0) Contact Trane Technical Support.
Rapid Restart Termination Time 180 Sec (120-600) Contact Trane Technical Support.
Rapid Restart DX Interstage Time 30 Sec (15-50)
Allows adjustment to the compressor
interstage time provi
ding an
accelerated or delayed staging.
Rapid Restart Critical Temp Setpoint 90°F (75-95)
Used to determine the compressor
stage target dur
ing an active Rapid
Restart event.
Table 17. Service settings (continued)