RT-SVP011E-EN 49
TD7 Display
Rapid Restart Minimum Percent
Capacity
25.0% (20.0-100)
Used to set the minimum compressor
stage regardle
ss of Critical Temp
Setpoint target needs.
Rapid Restart Control Band Setting 20.0°F (5.0-40.0) Contact Trane Technical Support.
Rapid Restart Mixed Air Temp. Low
Li
mit
42.0°F (40.0-55.0) C
ontact Trane Technical Support.
External Heat Supply Fan Speed
Setpoint
100.0% (0.0-1
00.0)
Sets the minimum supply fan speed for
s in g l
e z o n e h e a t i n g . H igh e r s p e e d s a r e
allowed.
Electrical Service Type Command Wye (Delta, Wye)
Used to identify the applied 3-phase
power connection
to the unit for power
meter applications.
Outdoor Air Damper Min. Voltage 2.0 V (0.0-9.9)
Minimum voltage setting for the
applied damp
er actuator equating to
fully closed.
Outdoor Air Damper Max. Voltage 10.0 V (2.1-10.0)
Maximum voltage setting for the
applied damp
er actuator equating to
fully open.
Outdoor Air Damper Direct/Reverse
Acting
Direct
(Direct, Reverse)
Sets damper position (P) stroke
direction.
Does Pmin P m a x e q u a t e t o
Vmin Vmax, or Vmax Vmin.
Outdoor Air Damper Stroke Time 30 Sec (1-255)
The time it takes for the actuator to
stroke from
Pmin to Pmax.
Relief Air Damper Min. Voltage 2.0 V (0.0-9.9)
Minimum voltage setting for the
applied damp
er actuator equating to
fully closed.
Relief Air Damper Max. Voltage 10.0 V (2.1-10.0)
Maximum voltage setting for the
applied damp
er actuator equating to
fully open.
Relief Air Damper Direct/Reverse
Acting
Direct
(Direct, Reverse)
Sets damper position (P) stroke
direction.
Does Pmin P m a x e q u a t e t o
Vmin Vmax, or Vmax Vmin.
Relief Air Damper Stroke Time 30 Sec (1-255)
The time it takes for the actuator
position (P)
to stroke from Pmin to
Pmax.
Condenser Reheat Valve Min. Position
Setpoint
15.0% (10.0-3
5.0) Contact Trane Technical Support.
Condenser Reheat Valve Max. Position
Setpoint
85.0% (40-100.0) Co
ntact Trane Technical Support.
Condenser Cooling Valve Min. Position
Setpoint
15.0% (10.0-3
5.0) Contact Trane Technical Support.
Condenser Cooling Valve Max. Position
Se
tpoint
85.0% (40-100.0) Contact Trane Technical Support.
Duct Static Pressure Control Prop Gain 13.2 (0.1-1000.0) Contact Trane Technical Support.
Duct Static Pressure Control Integral
Time
5 Sec (0-3600) C
ontact Trane Technical Support.
Duct Static Pressure Deadband 0.50 IWC (0.00-4.01)
DB. Control deadband around the
static pressure
setpoint. Control band
is Stp+1/2DB to Stp-1/2DB.
Space Static Pressure Control Prop
Gain
24.0 (0.5-500.0) Contact Trane Technical Support.
Space Static Pressure Integral Time 2.0 Sec (0.1-1000.0) Contact Trane Technical Support.
Space Static Pressure Control
De
adband
0.04 IWC (0.02-0.40)
DB.
Control deadband around the
static pressure
setpoint. Control band
is Stp+1/2DB to Stp-1/2DB.
Table 17. Service settings (continued)