50 RT-SVP011E-EN
TD7 Display
Space Static Press Control Feed
Forward
80.0% (0.0-100.0) Contact Trane Technical Support.
Outdoor Air Flow Calibration Gain 1 1.000 (0.250-1.750)
Used to allow modification to airflow
calculation base
d on local methods of
determining airflow.
Outdoor Air Flow Calibration Offset 1 0.0 cfm (-2500.0-2500.0)
Used to allow modification to airflow
calculation base
d on local methods of
determining airflow.
Outdoor Air Flow Calibration Gain 2 1.000 (0.250-1.750)
Used to allow modification to airflow
calculation base
d on local methods of
determining airflow.
Outdoor Air Flow Calibration Offset 2 0.0 cfm (-2500.0-2500.0)
Used to allow modification to airflow
calculation base
d on local methods of
determining airflow.
Traq Flow Control Proportional Gain 0.750 (0.050-10.000) Contact Trane Technical Support.
Traq Flow Control Integral Time 35 Sec (2-300) Contact Trane Technical Support.
Minimum Outdoor Air Flow Deadband 5.0% (1.0-25.0)
Control deadband (DB) around the
mi
nimum airflow se
tpoint. Control
band is Stp+1/2DB to Stp-1/2DB.
Econ Discharge Air Control Prop Gain 3.600 (0.100-100.000) Contact Trane Technical Support.
Econ Discharge Air Control Integral
Ti
me
75 Sec (1-3600) C
ontact Trane Technical Support.
Compressor Cooling Discharge Air
Mode Prop
ortional Gain
3.600 (0.100-100.000) Contact Trane Technical Support.
Compressor Cooling Discharge Air
Mode Inte
gral Time
100 Sec (1-3600) Contact Trane Technical Support.
Compressor Discharge Sat Temp. Limit
Filter Time
5
Sec (1-300) Contact Trane Technical Support.
Compressor Discharge Sat Temp. Limit
Threshold
147 °F (131.0-147.0) C
ontact Trane Technical Support.
Space Temp Cooling Proportional
Gain 4.000 (0.100-10.000) Contact Trane Technical Support.
Space Temp Cooling Integral Time 1200 Sec (990-3600) Contact Trane Technical Support.
Space Temp Heating Proportional Gain 4.000 (0.100-10.000) Contact Trane Technical Support.
Space Temperature Heating Integral
Time
1200 Sec (90-3600) C
ontact Trane Technical Support.
Heating Min Discharge Air Flow
Setpoint
100.0% (50.0-100.0) Co
ntact Trane Technical Support.
Temp. Control Staging Prop Gain
Cooling
6.000 (0.100-100.000) Co
ntact Trane Technical Support.
Temp. Control Staging Integral Time
Cool
50.0 Sec (0.1-3600.0) C
ontact Trane Technical Support.
Temp. Control Staging Deadband
Cooling
70.0% (10.0-1
00.0) Contact Trane Technical Support.
Occupied Space Temp. Reheat Prop
Gain
4.000 (0.100-10.000) Contact Trane Technical Support.
Occupied Space Temp. Reheat Integral
Time
1200.0 Sec
(90.0-3600) Contact Trane Technical Support.
Occupied Space Dehumidification
Proportional
Gain
3.000 (0.000-10.000) Contact Trane Technical Support.
Occupied Space Dehumidification Bias 55 °F (40.0-74.0) Contact Trane Technical Support.
Temp Control Staging Proportional
Gain Heating
2.000 (0.100-100.000) Contact Trane Technical Support.
Table 17. Service settings (continued)
Value Factory Default (Range) Description