TD7 Display
Temp. Control Staging Integral Time
Heat
50.0 Sec (0.1-3600.0) Contact Trane Technical Support.
Temp. Control Staging Deadband
Heating
1.0 °F
(0.0-36.0) Contact Trane Technical Support.
Heating Modulating Prop Gain 1.800 (0.100-100.000) Contact Trane Technical Support.
Heating Modulating Integral Time 100 Sec (1-3600) Contact Trane Technical Support.
Temperature Control Modulating
De
adband
2.0 °F
(0.0-180.0) Contact Trane Technical Support.
Condenser Fan Control Feedforward
Gain
1.000 (0.000-1.000) Contact Trane Technical Support.
Condenser Fan Control Integral Gain 1.000 (0.000-1.000) Contact Trane Technical Support.
Condenser Fan Damping Coefficient 10.000 (0.000-100.000) Contact Trane Technical Support.
Condenser Reheat Staging
Prop
ortional
Gain
6.000 (0.100-100.000) Contact Trane Technical Support.
Condenser Reheat Staging Int Time 50.0 Sec (0.1-3600.0) Contact Trane Technical Support.
Condenser Fan Staging Deadband 4.5 °F (1.8-9.0) Contact Trane Technical Support.
Condenser Reheat Modulation Prop
Gain
3.600 (0.100-100.000) Contact Trane Technical Support.
Condenser Reheat Mode Integral Time 90.0 Sec (0.1-3600.0) Contact Trane Technical Support.
Suction Superheat Proportional Gain 0.018 (0.000-0.200) Contact Trane Technical Support.
Suction Superheat Integral Time 80.0 Sec (0.0-200.0) Contact Trane Technical Support.
Suction Superheat Derivative Time 30.0 Sec (0.0-60.0) Contact Trane Technical Support.
Suction Pressure Proportional Gain 2.000 (0.000-10.000) Contact Trane Technical Support.
Suction Pressure Integral Time 20.0 Sec (0.0-200.0) Contact Trane Technical Support.
Suction Pressure Tracking Time 10.0 Sec (0.0-200.0) Contact Trane Technical Support.
Evap. Coil Frost Limit Proportional Gain 3.600 (0.100-20.000) Contact Trane Technical Support.
Evap. Coil Frost Limit Integral Time 60 Sec (1-600) Contact Trane Technical Support.
Evap. Coil Frost Delta 8.0 °F (3.0-20.0) Contact Trane Technical Support.
Evap. Coil Frost Threshold 28.0 °F (25.0-35.0) Contact Trane Technical Support.
Superheat High Limit 55.0 °F (50.0-65.0) Contact Trane Technical Support.
Compressor Discharge Sat Temp. Limit
Prop
ortional
Gain
2.0 (0.1-20.0) Contact Trane Technical Support.
Compressor Discharge Sat Temp. Limit
Integral Time
60.0 Sec
(1.0-600.0) Contact Trane Technical Support.
Compressor Discharge Sat Temp. Limit
Activation
Band
5 °F (3.0-18.0) Contact Trane Technical Support.
Compressor Discharge Pressure Limit
Unload Setpoint
97.0% (85.0-1
05.0) Contact Trane Technical Support.
Compressor Discharge Press Limit
Hold Se
tpoint
85.0% (75.0-90.0) Contact Trane Technical Support.
Compressor Speed Range Limit Slew
Rate
60 (10-120) Contact
Trane Technical Support.
CIPD Mod Limit Proportional Gain 0.500 (0.100-2.000) Contact Trane Technical Support.
CIPD Mod Limit Integral Time 30 Sec (1-600) Contact Trane Technical Support.
Hot Gas Bypass Pressure Ratio
Proportional
Band
0.500 (0.100-1.000) Contact Trane Technical Support.
Hot Gas Bypass Proportional Band 7.0 °F (1.0-20.0) Contact Trane Technical Support.
Table 17. Service settings (continued)
Value Factory Default (Range) Description