RT-SVP011E-EN 95
Troubleshooting
Software High Pressure
Detection CktX
where X is “1” or “2”
Circuit Warning Non-Latching
The discharge pressure, as measured discharge
pressure sensor, has exceeded 630 PSIA.
This warning is generated to give additional
information that could be used to determine why all
compressors on the circuit shut down due to an
Unexpected Compressor Shutdown diagnostic or why
a Compressor Failed to Start diagnostic is generated.
Even if the pressure has dropped below 630 PSIA the
h
istoric diagnostics will still indicate that a high
pressure was detected.
Local
Space CO2 Sensor Unit Warning Non-Latching
Space CO2 sensor has failed out of range.
DCV control will be inhibited.
Remote
Space Humidity Sensor Unit Warning Non-Latching
The Space Humidity sensor has failed out of range.
No action is taken for this sensor failure only the
Outdoor Air Humidity Sensor Active has special
action.
Remote
Space Humidity Sensor
Active
Unit Warning Non-Latching
The Space Humidity sensor value not available.
Dehumidification and humidification will be disabled.
This drives a ‘fall back’ response to Economizer
Enthalpy decision.
Remote
Space Pressure Sensor Unit Warning Latching
Space Pressure sensor has failed out of range.
Statitrac control will be terminated and the Relief Fan
Speed and Relief Damper command will fall back to
OA Damper Tracking.
Remote
Space Temp Cooling
Setpoint Wired
Unit Warning Non-Latching
The input to the Hex IO module has failed.
The unit will fall back to the “Space Temp Cooling
Setpoint Default” setting on the front panel.
Remote
Space Temp Heating
Setpoint Wired
Unit Warning Non-Latching
The input to the Hex IO module has failed.
The unit will fall back to the “Space Temp Heating
Setpoint Default” setting on the front panel.
Remote
Space Temperature
Invalid Active
Unit
VVZT/CVZT:
Normal
Shutdown
VVDA/CVDA:
Warning
Non-Latching
VVZT/CVZT: Unit Shutdown
VVDA/CVDA: Unit continues to operate and disables
the following functions:
All Unoccupied modes (heat, cool, DH),
Daytime Warmup,
Morning Warmup
Pre Cool
Space Temperature
Sensor
Unit Warning Non-Latching
The Space Temperature sensor input is out of range.
Multi-zone: If Space Temperature Active is invalid, all
functions requiring space temperature will be
inhibited.
Single-zone: Unit operation will be inhibited.
Remote
Starts/Hours Modified -
CprsrXY
where X is “1” or “2”
where Y is “A, “B” or
“C
Cprsr Warning Non-Latching
The circuit X compressor Y cumulative value of starts
and or hours have been modified by a write override
from TU.
No unit response.
Remote
Diagnostics Target Severity Persistence Condition / Response Reset Level