RT-SVP011E-EN 97
Troubleshooting
Unit Not Economizing
When It Should
Unit Warning Non- Latching
The unit is in active economizer cooling. The
economizer (OAD) command has been greater than
the economizer position by 10% for 5 continuous
minutes.
No unit response.
Remote
Ventilation Override
Mode A
Unit Warning Non-Latching
The unit is actively in a VOM A event with outputs
commanded per the settings entered at the Front
Panel.
(Default setting: Unit Off)
Local
Ventilation Override
Mode B
Unit Warning Non-Latching
The unit is actively in a VOM B event with outputs
commanded per the settings entered at the Front
Panel.
(Default setting: Pressurize)
Local
Ventilation Override
Mode C
Unit Warning Non-Latching
The unit is actively in a VOM C event with outputs
commanded per the settings entered at the Front
Panel.
(Default setting: Relief)
Local
Ventilation Override
Mode D
Unit Warning Non-Latching
The unit is actively in a VOM D event with outputs
commanded per the settings entered at the Front
Panel.
(Default setting: Purge)
Local
Ventilation Override
Mode E
Unit Warning Non-Latching
The unit is actively in a VOM E event with outputs
commanded per the settings entered at the Front
Panel.
(Default setting: Purge w/ Duct Static Pressure Cntl)
Local
VFD Compressor
Ground Fault– Cprsr1A
Circuit
Immediate
Shutdown
Latching*
An earth ground fault has resulted in a discharge
from the output phases to ground, either in the cable
between the adjustable frequency drive and the
motor or in the motor itself. Further compressor
operation is not recommended until measurements
to ground can be taken from the motor leads and the
ground fault removed.
* The Latching behavior for this
diagnostic is latched
in the drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio™ 800
controller by setting its persistence to Non-Latching.
This drive alarm may be Trip Locked at the TR200
d
rive. If the drive determines that the condition could
cause damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by
cycling power.
Local
VFD Compressor High
Pr
essure Trip – Cprsr1A
Circuit
Immediate
Shutdown
Latching*
The drive safe stop input was activated. This trip is
the result of a high pressure cutout. The high
pressure switch must reset once the pressure has
dropped and a manual reset must be commanded at
the user interface before the circuit will be allowed to
restart. This diagnostic may require a power cycle to
reset the TR200 drive (Safe Stop) alarm.
* The Latching behavior for this
diagnostic is latched
in the drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio™ 800
controller by setting its persistence to Non-Latching.
This diagnostic may require a power cycle to reset the
TR200 dr
ive (Safe Stop) alarm.
Local
Diagnostics Target Severity Persistence Condition / Response Reset Level