Induced Draft Motors
Step 4
Make sure the motor wheel spins freely and debris is
not preventing it from operating. If the motor wheel
spins freely, all motor winding combinations have
equal resistance and are not shorted to ground, the
motor is not at fault. Replace the furnace control
board.