Installation (for qualified installers only) 43
© Travis Industries 3/13/18 - 1474 42 & 54PB GSB2 Aust.
Use of a Non-Combustible Mantel Below Listed Mantel Clearances
Each gas fireplace has a unique set of mantel requirements. If you wish to place a non-combustible
mantel at a lesser height than specified in this manual, it will need to meet the following requirements:
The header (the framing member above the fireplace opening) must be non-combustible.
The facing must be non-combustible and extend to the header (or mantel, whichever is greater).
The facing must also span the entire width of the mantel.
See the illustration below for additional requirements.