vacon • 100 Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.4.3 Group 3.3.4: Motor Potentiom
With a motor potentiometer function, the user can increase and decrease the output frequency. By
connecting a digital input to parameter P3.3.4.1 (
MotPot UP) and having the digital input signal ac-
tive, the output frequency will rise as long as the signal is active. The parameter P3.3.4.2 (
MotPot
DOWN
) works vice versa, decreasing the output frequency.
The rate how the output frequency either rises or falls when Motor Potentiometer Up or Down is
activated is determined by the
Motor potentiometer ramp time (P3.3.4.3)
The Motor potentiometer reset parameter (P3.3.4.4) is used to choose whether to reset (set to Min-
Freq) the Motor Potentiometer frequency reference when stopped or when powered down.
Motor potentiometer frequency reference is available in all control places in menu Group 3.3: Ref-
erences. The motor potentiometer reference can be changed only when the drive is in run state.
P3.3.3.7 Preset Freq 5 P3.3.1.1 P3.3.1.2 Hz 30.00 128
Select with digital inputs: Preset fre-
quency selection 0 & 2
P3.3.3.8 Preset Freq 6 P3.3.1.1 P3.3.1.2 Hz 40.00 129
Select with digital inputs: Preset fre-
quency selection 1 & 2
P3.3.3.9 Preset Freq 7 P3.3.1.1 P3.3.1.2 Hz 50.00 130
Select with digital inputs: Preset fre-
quency selection 0 & 1 & 2
P3.3.3.10 Preset Freq Sel0
DigIN
SlotA.4
419
Binary selector for Preset speeds (0-
7). See parameters P3.3.3.2 to
P3.3.3.9.
P3.3.3.11 Preset Freq Sel1
DigIN
SlotA.5
420
Binary selector for Preset speeds (0-
7). See parameters P3.3.3.2 to
P3.3.3.9.
P3.3.3.12 Preset Freq Sel2
DigIN
Slot0.1
421
Binary selector for Preset speeds (0-
7). See parameters P3.3.3.2 to
P3.3.3.9.
Table 67. Motor potentiometer parameters
Code Parameter Min Max Unit Default ID Description
P3.3.4.1 MotPot UP
DigIN
Slot0.1
418
FALSE = Not active
TRUE = Active (Motor potentiom-
eter reference INCREASES until
the contact is opened)
P3.3.4.2 MotPot DOWN
DigIN
Slot0.1
417
FALSE = Not active
TRUE = Active (Motor potentiom-
eter reference DECREASES until
the contact is opened)
P3.3.4.3 MotPot Ramp Time 0.1 500.0 Hz/s 10.0 331
Rate of change in the motor
potentiometer reference when
increased or decreased with
parameters P3.3.4.1 or P3.3.4.2.
P3.3.4.4 MotPot Reset 0 2 1 367
Motor potentiometer frequency
reference reset logic.
0 = No reset
1 = Reset if stopped
2 = Reset if powered down
Table 66. Preset frequencies parameters
Code Parameter Min Max Unit Default ID Description