User interfaces vacon • 51
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the lowest
priority and can be chosen with parameter P3.2.1
(Rem Control Place). I/O B, again, can bypass the
remote control place selected with parameter P3.2.1 using a digital input. The digital input is se-
lected with parameter P3.5.1.7
(I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control has higher priority than
remote control. Therefore, if, for example, bypassed by parameter P3.5.1.7 through digital input
while in
Remote, the control place will still switch to Keypad if Local is selected. Switching between
Local and Remote Control can be done by pressing the FUNCT-button on the keypad or by using the
"Local/Remote" (ID211) parameter.
Changing control places
Change of control place from
Remote to Local (keypad).
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the
Arrow up or the Arrow down button to select Local/Remote and confirm with the OK
button.
3. On the next display, select
Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the
FUNCT button was pushed. How-
ever, if the Remote control place was changed to Local (Keypad) you will be prompted for key-
pad reference.
Figure 18. Changing control places
Accessing the control page
The
Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the
FUNCT button.
2. Push the
Arrow up or the Arrow down button to select Control page and confirm with the OK
button.
3. The control page appears
If keypad control place and keypad reference are selected to be used you can set the
Keypad
Reference
after having pressed the OK button. If other control places or reference values are
used the display will show Frequency reference which is not editable. The other values on the
page are Multimonitoring values. You can choose which values appear here for monitoring (for
this procedure, see page 61).
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY Keypad
ID: M1
( 7 )
Monitor
( 6 )
ID:
Choose action
STOP Ready Keypad
ID:1805
Local/Remote
Control page
Change direction
?
Remote
ID:
Local/Remote
STOP READY Keypad
ID:211
Remote
Local
Main Menu
Parameters
( 15 )
Diagnostics
STOP READY I/O
ID: M1
( 7 )
Monitor
( 6 )
FUNCT
OK
OK
9161.emf