Initial Setup Of The Console Using Workflow Wizard Setup>Pumps and Lines>All PLLD
45
Setup>Pumps and Lines>All PLLD
This screen lets you setup test parameters for all pressurized line leak detectors.
Line Re-Enable Method
Determines what conditions allow you to re-enable the line.
Allowable selections:
• Pass Line Test - The line must pass the test in order to be enabled.
•Alarm Acknowledge - The line can be enabled after the alarm is acknowledged.
Periodic Test Warnings
Touch to enable or disable the Periodic Test Needed Warning/Alarm which informs you that
a line will soon be out of compliance because a Periodic test was not completed within the
required time. This lets you stop dispensing from the line until a Periodic test has been com-
pleted.
Days before Periodic Warning
The number of days before the Periodic Test Alarm Warning is triggered.
Allowable selection: 0 - 30 days (default is 25 days).
Days before Periodic Alarm
The number of days before the Periodic Test Needed Alarm is triggered.
Allowable selection: 0 - 30 days (default is 30 days).
Annual Test Needed Warnings
Touch to enable or disable the Annual Test Needed Warnings which informs you that a line
will soon be out of compliance because an Annual test was not completed within the
required time. This lets you stop dispensing from the line until an Annual test is completed.
Days before Annual Warning
The number of days before the Annual Test Needed Warning is triggered.
Allowable selection: 0 - 365 days (default is 355).
Days before Annual Alarm
The number of days before the Annual Test Needed Alarm is triggered.
Allowable selection: 0 - 365 days (default is 365)
Precision Test Delay (hours)
The number of hours between a passed periodic or annual
test and running the next line test(s).
NOTE: In previous TLS consoles, this was referred to as Pre-
cision Test Duration.
Allowable selection: 12 to 744 hours
NOTE: When CSLD is enabled for the tank assigned to the
line, a minimum value of 60 hours is used internally when the
precision test delay value is less than 60.
0.1 gph (0.38 lph) Line Test Auto Confirm
Touch to enable or disable the ability of the console to evalu-
ate several 0.1 gph (0.38 lph) line tests before a result is
posted. Enabling Auto Confirm reduces the risk of false test
results, but it extends the time that it may take to post
results.
0.2 gph (0.76 lph) Line Test Auto Confirm
Touch to enable or disable the ability of the console to evalu-
ate several 0.2 gph (0.76 lph) line tests before a result is
posted. Enabling Auto Confirm reduces the risk of false test
results, but it extends the time that it may take to post
results.
See the Actions>Help>Understanding Regulatory Compli-
ance In-Tank Leak Tests topic for more information.