Initial Setup Of The Console Using Workflow Wizard Setup>Headers
11
Setup>Headers
Setup>System>Alarm Filtering
This screen lets you enter information to identify your site location, address, phone number, etc. This infor-
mation appears on the top of most inventory and BIR reports. This screen also lets you enter a fax sender
name and fax number when sending faxes.
Header 1 - 4
Touch to enter desired Site Name (1),
Street (2), City and State (3) and Phone (4) -
up to 20 characters each header.
Fax Sender Name
Touch to enter data printed at top of trans-
mitted faxes from console - up to 30 alpha-
numeric characters.
Fax Phone Number
Touch to enter phone number to which the
console will dial to send faxes - up to 40
digits.
This screen lets you enable/disable Alarm Filtering. Alarm Filtering reduces the total num-
ber of alarms without compromising the reporting of critical alarms.
Alarm Filtering
When this feature is enabled, the console manipulates a combination of the detection time
(the time before an alarm sounds) and the clear time (the time before an alarm is reset) for
certain alarms that often go in and out of an alarm state in a short period of time. In addi-
tion, some alarm reports during the clear time are consolidated, reducing their number
without eliminating the alarm reports.
Mag Sensors
The following Mag Sensor alarms will be filtered:
• Mag sensor fault, install and communication alarms - NOTE:
Mag Sensor alarms are reset if the Mag Sensor is replaced
or deconfigured and then reconfigured.
Analog Sensors
The following Liquid, Vapor, Groundwater, Type A (2-wire) and
Type B (3-wire) alarms will be filtered:
• Open, Short, Water, Water Out, Liquid Warning, Low Liquid,
High Liquid and Fuel - NOTE: Liquid Warning, High Liquid,
Low Liquid and Fuel alarms are posted immediately even
when filtered.
DIMs (Dispenser Interface Modules)
The following DIM alarm will be filtered:
•Communication Alarm - NOTE: If there is more than one DIM
card in the console, each card is filtered independently. DIM
alarm filtering takes into account the possibility of lost POS
sales data by monitoring dispensing during the clear time,
but the possibility exists that the filter may not identify all
cases when POS sales data may be lost. Unfiltered DIM
Communication Alarm reports are available by contacting
Veeder-Root Technical Support.
Probes
The following Probe alarm will be filtered:
•Probe Out