Initial Setup Of The Console Using Workflow Wizard Setup>Tank>Environmental Test
30
Setup>Tank>Environmental Test
This screen provides a choice of selecting a tank test method (SLD, CSLD, or Disabled) for a
selected tank. Once a tank test method has been chosen, the corresponding setup parame-
ters for either SLD or CSLD are displayed, and you can enter settings by which the selected
test will be conducted.
Tank Test Method
Select the method for testing your tanks:
SLD (Static Leak Detection) - a single tank test (that runs on demand, at a programmed
time, or by pump sense signal) where there must be no dispensing during the test.
CSLD (Continuous Statistical Leak Detection) - leak tests that are run continuously during
idle tank times.
Disabled - no testing method has been enabled.
SLD
Leak Test Rate
Touch to select which leak rate test is printed:
0.2 gph (0.76 lph) Leak Test
0.1 gph (0.38 lph) Leak Test
NOTE: Both of the above tests, as well as the Gross Leak Test [(1.5 gph (5.8 lph)], are run
when you start the SLD tank test. This field determines what the system prints out for the
test results.
Periodic Test Type
Touch to select a periodic test type:
Standard - System runs the periodic leak test for the entire test duration before posting a
test result. The minimum wait time after delivery when a test can be run is 8 hours, and
the minimum test duration is 2 hours.
Quick - System runs the periodic leak test for the entire test duration before posting a test
result. The minimum wait time after delivery when a test can be run is 5 hours, and the
minimum test duration is 1 hour.
Test Frequency
Touch to select the frequency for SLD tests as described
below. Most local agencies require a minimum monthly (30
days) test.
Gross Test Auto-Confirm
Touch to enable or disable the ability of the console to
require two failed Gross Tests [(1.5 gph (5.8 lph)] before it
considers the test a failure. NOTE: When enabled, this fea-
ture may reduce false alarms.
Duration
Touch to enter the amount of time (in hours, from 2 - 24) for
the test to complete.
Leak Min. Periodic (% Full Volume)
Touch to enter a minimum tank volume required to record a
valid periodic test (value reflects federal, state, and local
requirements)
Field Range, Min, Max
Default Visible If:
Period On Date, Annually by
Day of Week,
Monthly by Day of
Week, Weekly, Daily,
Annually by Day of
Month, Monthly by
Day of Month, Auto
On Date Always
Set Date Month: 1-12, Day: 1-
31, Year: 1970 - 2038
Current
Date
If Period choice is On
Date
Month January - December
January If Period choice is
Annually by Day of Week,
Annually by Day of Month
Weekday Sunday - Saturday Sunday If Period choice is
Annually by Day of Week,
Monthly by Day of Week,
Weekly
Occurrence 1st, 2nd, 3rd, 4th,
Last
1st If Period choice is
Annually by Day of Week,
Monthly by Day of Week
Day of Month 1 - 31 1 If Period choice is
Annually by Day of Month,
Monthly by Day of Month
Time of Day Time in Hours and
Minutes, 12 Hr.
sensitive
Current time
+ 2 minutes
If Period choice is On
Date, Annually by Day of
Week, Annually by Day of
Month, Monthly by Day of
Week, Monthly by Day of
Month, Weekly, Daily

Table of Contents

Other manuals for Veeder-Root TLS-450PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-450PLUS and is the answer not in the manual?

Veeder-Root TLS-450PLUS Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-450PLUS
CategoryMusic Mixer
LanguageEnglish

Related product manuals