What to do if Vertiv Liebert CR012 compressor is over temperature?
M
Mary PrattSep 12, 2025
If the Vertiv Air Conditioner compressor is overheating, check the settings of the HP and LP switches, and inspect the condenser for clogs. Also, check that the fans of the evaporator and condenser are functioning normally. If the suction overheat degree is too high, regulate the EEV or add the proper amount of refrigerant.
B
Barbara WalshSep 13, 2025
What to do if Vertiv Liebert CR012 contactor does not get closed and the compressor does not start?
H
hardyjennySep 13, 2025
If the contactor doesn't close and the compressor doesn't start in your Vertiv Air Conditioner, check the state of the micro-processing controller for a low discharging overheat degree alarm. Also, check for a high-pressure (HP) alarm, a discharging low/high temperature alarm, or a low-pressure alarm in the history. Check if the contactor is able to energize and inspect the compressor driver.
J
john57Sep 15, 2025
What to do if Vertiv Liebert CR012 Air Conditioner compressor internal protector is open?
P
pbrownSep 15, 2025
Check whether the compressor coil is an open circuit. In such a scenario, wait till the coil is cooled following which it will be restored automatically.