3.2 Unit Weights
Model
Number of Fans
on Heat Rejection Skid
Number of MCV/PRE Pairs
onHeat Rejection Skid
Domestic Shipping Weight
lb(kg)
Dry Weight, lb (kg)
MCV330+PRE with Receiver 6 1
5,000
(2,268)
4,980
(2,258)
MCV330+PRE with Receiver 12 2
10,000
(4,535)
9,980
(4,526)
MCV440+PRE with Receiver 8 1
5,900
(2,676)
5,880
(2,667)
MCV440+PRE with Receiver 16 2
11,580
(5,252)
11,560
(5,243)
MCV440 + PRE without Receiver 8 1
5,800
(2,676)
5,780
(2.621)
MCV440 + PRE without Receiver 16 2
11,380
(5,252)
11,360
(5,152)
MCV430 + PRE without Receiver 6 1 6,190 (2,808) 6,170 (2,799)
MCV430 + PRE without Receiver 12 2 11,980 (5,434) 11,960 (5,425)
Table 3.2 Vertiv™ Liebert® MCV Heat Rejection Skid with Vertiv™ Liebert® EconoPhase Approximate Weights
3 Pre-installation
PreparationandGuidelines
Proprietary and Confidential ©2024 Vertiv Group Corp. 11
Vertiv™ Liebert® MCV Installer/User Guide