EasyManua.ls Logo

Vertiv Liebert MCV440 - 6.3 Wye vs. Delta Connected Power Supply for Alternative EC Fans

Vertiv Liebert MCV440
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.3 Wye vs. Delta Connected Power Supply for Alternative EC Fans
Figure 6.1 Power Supply Requirements for 380V-575V Units: Acceptable
Figure 6.2 Unacceptable
NOTE: The 380-575 volt unit is designed to operate with Wye-connected power with a solidly grounded neutral. It will
not operate properly with Wye-connected power with high-resistance (or impedance) ground or with Delta-connected
power. A separate neutral wire is not required to be run to the Liebert® MCV Condenser.
Acceptable Power Supplies—380-575V Nominal Units
380-575V wye with solidly grounded neutral and 277V line-to-neutral