Model Voltage FLA WSA OPD
MCV440 + PRE
2 = 380V/60Hz 36.4 37.5 40
A = 460V/60Hz 29.4 30.3 35
G = 415V/50Hz 35.4 36.3 40
B = 575V/60Hz 23.5 24.2 35
MCV430 + PR250
2 = 380V/60Hz 29.4 30.5 35
A = 460V/60Hz 23.8 24.7 25
G = 415V/50Hz 28.5 29.3 30
B = 575V/60Hz 19.0 19.7 30
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
Source: DPN005045, Rev. 4
Table 6.3 Heat Rejection Skid Electrical Data, 3 Phase (continued)
NOTE: Heat rejection skids with 12 or 16 fans contain two 3 phase connection boxes, and each box requires a separate
supply input per Table 6.3 below.
6.2 Wye vs. Delta Connected Power Supply for ECFans
Acceptable Power Supplies—380V to 460V Nominal Units
380V wye with solidly grounded neutral and 220V line to ground
480V wye with solidly grounded neutral and 277V line to ground
Wye with high resistance (or impedance) ground
Delta with corner ground
Unacceptable Power Supplies
Delta without ground or with floating ground
Delta with grounded center tap