EasyManua.ls Logo

Viessmann VITOCAL 250-A - Page 153

Viessmann VITOCAL 250-A
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
153
Measures
1. Check the sensor and the following connections:
■
Terminals X17.1/X17.2 on EHCU electronics mod-
ule
■
Wall mounted indoor unit:
6-pole connection socket on underside of appli-
ance on left, terminals 5 and 6
■
Floorstanding indoor unit:
Extra low voltage (ELV) terminal area < 42 V,
lower luster terminal, terminals 7 and 8
■
Check wires and plugs for correct seating.
■
Check connections for contact corrosion.
■
Check cables for mechanical damage, e.g. crush-
ing, kinking, chafing or breakage.
2. Check resistor R for NTC 10 kΩ on the disconnected
plug. If R < 500 Ω, replace the sensor.
3. Replace EHCU electronics module.
F.993 Lead break, temperature sensor in heating/cooling water buffer cylinder
F.993
System characteristics
No heating/cooling of external heating/cooling water
buffer cylinder
Cause
Only for heat pumps with 1 integral heating/cooling cir-
cuit:
Lead break, temperature sensor in heating/cooling
water buffer cylinder
Measures
1. Check the following connections:
■
Terminals X17.1/X17.2 on EHCU electronics mod-
ule
■
Wall mounted indoor unit:
6-pole connection socket on underside of appli-
ance on left, terminals 5 and 6
■
Floorstanding indoor unit:
Extra low voltage (ELV) terminal area < 42 V,
lower luster terminal, terminals 7 and 8
■
Check wires and plugs for correct seating.
■
Check connections for contact corrosion.
■
Check cables for mechanical damage, e.g. crush-
ing, kinking, chafing or breakage.
2. Check resistor R for NTC 10 kΩ on the disconnected
plug. If R > 300 kΩ, replace the sensor.
3. Replace EHCU electronics module.
F.994 Short circuit, temperature sensor in heating water buffer cylinder
F.994
System characteristics
No heating of external heating water buffer cylinder
Cause
Only for heat pumps with 1 integral heating/cooling cir-
cuit:
Short circuit, temperature sensor in heating water buf-
fer cylinder
Messages
Fault messages (cont.)
6218234
Diagnosis

Table of Contents