77
If the calculation results in a lower set flow temperature
than the value set here, the set flow temperature will
be limited to this value.
This value cannot be set higher than max. value in
parameter 1194.1.
1194.1 Max. flow temperature, heating, heating/cooling circuit 3
Set flow temperature limit for heating mode via heat-
ing/cooling circuit 3
The set flow temperature for heating mode results from
the following:
Weather-compensated heating mode: In line with the
set heating curve and the set room temperature
Room temperature-dependent heating mode (room
temperature sensor required): From the differential
between the set and the actual room temperature
If the calculation results in a higher set flow tempera-
ture than the value set here, the set flow temperature
will be limited to this value.
Note
Since the heat pump control unit only limits the set
value with this parameter, a temperature limiter for
restricting the maximum temperature (accessories)
must be installed in the flow of an underfloor heating
circuit.
1195 Set flow temperature limits, heating/cooling circuit 4
1195.0 Min. flow temperature, heating, heating/cooling circuit 4
Set flow temperature limit for heating mode via heat-
ing/cooling circuit 4
The set flow temperature for heating mode results from
the following:
Weather-compensated heating mode: In line with the
set heating curve and the set room temperature
Room temperature-dependent heating mode (room
temperature sensor required): From the differential
between the set and the actual room temperature
If the calculation results in a lower set flow temperature
than the value set here, the set flow temperature will
be limited to this value.
This value cannot be set higher than max. value in
parameter 1195.1.
1195.1 Max. flow temperature, heating, heating/cooling circuit 4
Set flow temperature limit for heating mode via heat-
ing/cooling circuit 4
The set flow temperature for heating mode results from
the following:
Weather-compensated heating mode: In line with the
set heating curve and the set room temperature
Room temperature-dependent heating mode (room
temperature sensor required): From the differential
between the set and the actual room temperature
If the calculation results in a higher set flow tempera-
ture than the value set here, the set flow temperature
will be limited to this value.
Note
Since the heat pump control unit only limits the set
value with this parameter, a temperature limiter for
restricting the maximum temperature (accessories)
must be installed in the flow of an underfloor heating
circuit.
1232 Configuration of general digital input 1
1232.0 Function of digital input 1
For the potential-free contact connected to digital
input 1 (connection 143.2), the following functions can
be specified:
Value Meaning
0 No function
Parameter group for heating/cooling circuit
1194 Set flow temperature limits,… (cont.)