75
1102.1 Heating circuit pump max. speed, heating/cooling circuit 1
Only change the factory setting if the minimum flow
rate in heating/cooling circuit 1 is not reached: See
chapter "Flow rate control with Hydro AutoControl".
Maximum speed of the internal heating circuit pump for
room heating/room cooling, heating/cooling circuit 1
1102.2 Heating circuit pump set speed, heating/cooling circuit 1
Set speed of the internal heating circuit pump for room
heating/room cooling, heating/cooling circuit 1
1103 Speed settings for heating circuit pump, heating/cooling circuit 2
Note
See also chapter "Flow rate control with Hydro Auto-
Control".
1103.0 Heating circuit pump min. speed, heating/cooling circuit 2
Minimum speed of the internal heating circuit pump for
room heating/room cooling, heating/cooling circuit 2
1103.1 Heating circuit pump max. speed, heating/cooling circuit 2
Maximum speed of the internal heating circuit pump for
room heating/room cooling, heating/cooling circuit 2
1103.2 Heating circuit pump set speed, heating/cooling circuit 2
Only change the factory setting if the minimum flow
rate in heating/cooling circuit 2 is not reached: See
chapter "Flow rate control with Hydro AutoControl".
Set speed of the internal heating circuit pump for room
heating/room cooling, heating/cooling circuit 2
1192 Set flow temperature limits, heating/cooling circuit 1
1192.0 Min. flow temperature, heating, heating/cooling circuit 1
Set flow temperature limit for heating mode via heat-
ing/cooling circuit 1
The set flow temperature for heating mode results from
the following:
■
Weather-compensated heating mode: In line with the
set heating curve and the set room temperature
■
Room temperature-dependent heating mode (room
temperature sensor required): From the differential
between the set and the actual room temperature
If the calculation results in a lower set flow temperature
than the value set here, the set flow temperature will
be limited to this value.
This value cannot be set higher than max. value in
parameter 1192.1.
1192.1 Max. flow temperature, heating, heating/cooling circuit 1
Set flow temperature limit for heating mode via heat-
ing/cooling circuit 1
Parameter group for heating/cooling circuit
1102 Speed settings for heating circuit pump,… (cont.)
6218234
Parameter