Viessmann VITOCAL 250-A - 1395 Heating Limit: Economy Function, Outside Temperature, Heating; Cooling Circuit 1; 1395.0 Enable Summer Economy Control, Heating;Cooling Circuit 1; 1395.1 Summer Saving Temperature Threshold, Heating;Cooling Cir- Cuit 1; 1396 Heating Limit: Economy Function, Outside Temperature, Heating; Cooling Circuit 2

Viessmann VITOCAL 250-A
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
78
Value Meaning
1 External demand, DHW circulation pump
If the connected button is pressed, the DHW
circulation pump runs for the duration set in
parameter 497.4.
2 External blocking
Refrigerant circuit, instantaneous heating wa-
ter heater and external heat generator (if in-
stalled) are blocked.
3 Blocking heating/cooling circuit 1.
If the temperature limiter for restricting the
maximum temperature for underfloor heating
circuit 1 responds, the room heating for this
heating/cooling circuit is switched off.
1395 Heating limit: Economy function, outside temperature, heating/cooling circuit 1
1395.0 Enable summer economy control, heating/cooling circuit 1
Heating limit, heating/cooling circuit 1:
The economy function can be activated so that the
rooms are not heated unnecessarily when outside tem-
peratures are mild. The required limit temperature
(heating limit) for the economy function is set for heat-
ing/cooling circuit 1 with parameter 1395.1.
If the adjusted outside temperature (parame-
ter 919.0) exceeds the limit temperature by 2 K,
room heating is switched off. The heating circuit
pump is off.
If the adjusted outside temperature falls 2 K below
the limit temperature, room heating is switched on.
The heating circuit pump is running.
Value Meaning
0 Economy function inactive
1 Economy function active
1395.1 Summer saving temperature threshold, heating/cooling circuit 1
Heating limit for economy function, outside tempera-
ture, heating/cooling circuit 1:
The economy function can be activated so that the
rooms are not heated unnecessarily when outside tem-
peratures are mild (parameter 1395.0). The required
limit temperature (heating limit) is set for heating/cool-
ing circuit 1 in this parameter.
If the adjusted outside temperature (parame-
ter 919.0) exceeds the limit temperature by 2 K,
room heating is switched off. The heating circuit
pump is off.
If the adjusted outside temperature falls 2 K below
the limit temperature, room heating is switched on.
The heating circuit pump is running.
1396 Heating limit: Economy function, outside temperature, heating/cooling circuit 2
1396.0 Enable summer economy control, heating/cooling circuit 2
Heating limit, heating/cooling circuit 2:
The economy function can be activated so that the
rooms are not heated unnecessarily when outside tem-
peratures are mild. The required limit temperature
(heating limit) is set for heating/cooling circuit 1 with
parameter 1396.1.
If the adjusted outside temperature (parame-
ter 919.0) exceeds the limit temperature by 2 K,
room heating is switched off. The heating circuit
pump is off.
If the adjusted outside temperature falls 2 K below
the limit temperature, room heating is switched on.
The heating circuit pump is running.
Parameter group for heating/cooling circuit
1232 Configuration of general digital input 1 (cont.)
6218234
Parameter