82
2406.0 Set flow temperature for cooling, heating/cooling circuit 2
Effective set flow temperature for cooling mode via
heating/cooling circuit 2
■
Upon demand via the set room temperature, cooling
is performed with the flow temperature set here.
Note
If the cooling circuit type is reset in the commission-
ing assistant, the corresponding factory-set flow tem-
perature from parameter 2405.1 or 2405.2 will be
adopted initially.
■
The value cannot be set lower than the value in
parameter 2410.0 or higher than the value in param-
eter 2410.1.
2406.1 Set flow temperature, cooling, underfloor heating circuit, heating/cooling circuit 2
Do not adjust!
Factory-selected set flow temperature for cooling via
heating/cooling circuit 2
Requirement: Heating/cooling circuit 2 is configured as
an underfloor heating circuit.
2406.2 Set flow temperature, cooling with fan convector, heating/cooling circuit 2
Do not adjust!
Factory-selected set flow temperature for cooling via
heating/cooling circuit 2
Requirement: Heating/cooling circuit 2 is configured as
a fan convector.
2407 Constant set flow temperature, heating/cooling circuit 3
2407.0 Set flow temperature for cooling, heating/cooling circuit 3
Effective set flow temperature for cooling mode via
heating/cooling circuit 3
■
Upon demand via the set room temperature, cooling
is performed with the flow temperature set here.
Note
If the cooling circuit type is reset in the commission-
ing assistant, the corresponding factory-selected set
flow temperature from 2405.1 or 2405.2 will be adop-
ted initially.
■
The value cannot be set lower than the value in
parameter 2411.0 or higher than the value in param-
eter 2411.1.
2407.1 Set flow temperature, cooling, underfloor heating circuit, heating/cooling circuit 3
Do not adjust!
Factory-selected set flow temperature for cooling via
heating/cooling circuit 3
Requirement: Heating/cooling circuit 3 is configured as
an underfloor heating circuit.
2407.2 Set flow temperature, cooling with fan convector, heating/cooling circuit 3
Do not adjust!
Factory-selected set flow temperature for cooling via
heating/cooling circuit 3
Requirement: Heating/cooling circuit 3 is configured as
a fan convector.
Parameter group for heating/cooling circuit
2406 Constant set flow temperature, heating/cooling circuit 2
6218234
Parameter