86
2413.0 Start condition, cooling, heating/cooling circuit 1
Start condition for operation of the heating circuit pump
in heating/cooling circuit 1 for weather-compensated
room cooling:
If the adjusted outside temperature exceeds the set
room temperature selected plus the value set here, the
circulation pump switches on.
2413.1 Stop condition, cooling, heating/cooling circuit 1
Stop condition for operation of the heating circuit pump
in heating/cooling circuit 1 for weather-compensated
room cooling:
If the adjusted outside temperature falls below the
selected set room temperature by the value set here,
the circulation pump switches off.
2414 Threshold value, cooling activation and deactivation, heating/cooling circuit 2
2414.0 Start condition, cooling, heating/cooling circuit 2
Start condition for operation of the heating circuit pump
in heating/cooling circuit 2 for weather-compensated
room cooling:
If the adjusted outside temperature exceeds the set
room temperature selected plus the value set here, the
circulation pump switches on.
2414.1 Stop condition, cooling, heating/cooling circuit 2
Stop condition for operation of the heating circuit pump
in heating/cooling circuit 2 for weather-compensated
room cooling:
If the adjusted outside temperature falls below the set
room temperature by the value set here, the circulation
pump switches off.
2415 Threshold value, cooling activation and deactivation, heating/cooling circuit 3
2415.0 Start condition, cooling, heating/cooling circuit 3
Start condition for operation of the heating circuit pump
in heating/cooling circuit 3 for weather-compensated
room cooling:
If the adjusted outside temperature exceeds the set
room temperature selected plus the value set here, the
circulation pump switches on.
2415.1 Stop condition, cooling, heating/cooling circuit 3
Stop condition for operation of the heating circuit pump
in heating/cooling circuit 3 for weather-compensated
room cooling:
If the adjusted outside temperature falls below the
selected set room temperature by the value set here,
the circulation pump switches off.
2416 Threshold value, cooling activation and deactivation, heating/cooling circuit 4
2416.0 Start condition, cooling, heating/cooling circuit 4
Start condition for operation of the heating circuit pump
in heating/cooling circuit 4 for weather-compensated
room cooling:
If the adjusted outside temperature exceeds the set
room temperature selected plus the value set here, the
circulation pump switches on.
Parameter group for heating/cooling circuit
2413 Threshold value, cooling activation and deactivation, heating/cooling circuit 1
6218234
Parameter