2426.0 Enable economy function, outside temperature, heating/cooling circuit 1
Energy saving function for the heating circuit pump of
heating/cooling circuit 1 for weather-compensated cen-
tral heating
Value Meaning
0 Energy saving function off
1 Energy saving function on:
If the adjusted outside temperature ex-
ceeds the set room temperature plus the
value in parameter 2426.1, the circulation
pump switches off.
If the adjusted outside temperature falls
below the set room temperature plus the
value in parameter 2426.1 1 K, the circu-
lation pump switches back on.
2426.1 Hysteresis, economy function, outside temperature, heating/cooling circuit 1
Hysteresis for energy saving function of the heating
circuit pump of heating/cooling circuit 1 for weather-
compensated central heating:
Energy saving function is active if parameter 2426.0 is
set to 1.
Conditions for starting and stopping the heating circuit
pump:
If the adjusted outside temperature exceeds the set
room temperature plus the value in parame-
ter 2426.1, the circulation pump switches off.
If the adjusted outside temperature falls below the
set room temperature plus the value in parame-
ter 2426.1 1 K, the circulation pump switches back
on.
2427 Energy saving function, heating/cooling circuit 2
2427.0 Enable economy function, outside temperature, heating/cooling circuit 2
Energy saving function for the heating circuit pump of
heating/cooling circuit 2 for weather-compensated cen-
tral heating
Value Meaning
0 Energy saving function off
1 Energy saving function on:
If the adjusted outside temperature ex-
ceeds the set room temperature plus the
value in parameter 2427.1, the circulation
pump switches off.
If the adjusted outside temperature falls
below the set room temperature plus the
value in parameter 2427.1 1 K, the circu-
lation pump switches back on.
2427.1 Hysteresis, economy function, outside temperature, heating/cooling circuit 2
Hysteresis for energy saving function of the heating
circuit pump of heating/cooling circuit 2 for weather-
compensated central heating:
Energy saving function is active if parameter 2427.0 is
set to 1.
Conditions for starting and stopping the heating circuit
pump:
If the adjusted outside temperature exceeds the set
room temperature plus the value in parame-
ter 2427.1, the circulation pump switches off.
If the adjusted outside temperature falls below the
set room temperature plus the value in parame-
ter 2427.1 1 K, the circulation pump switches back
on.
Parameter group for heating/cooling circuit
2426 Energy saving function, heating/cooling circuit 1
6218234
Parameter