Vigilant MX1-Au Operator Manual Document: LT0439
Page 23 October 2018 Issue 1.73
9-12
Fig 9-13 Silence/Resound Alarms Example Display
The first line will display the SID of the panel you are using. The second
line will display the site name.
Press NEXTF3 or PREVF2 to step on to the required panel.
If the alarm devices at the remote panel have been activated (i.e., its
ALARM DEVICES ACTIVATED LED is on) then Activated will be
displayed in the fourth line as shown in the example in Figure 9.14.
Fig 9-14 Silence/Resound Alarms Example Display
Press
SILENCE F1 to silence the alarm devices at that MX1.
DISABLE F4 to disable the alarm devices at that MX1. A
confirmation screen will be shown. Press OK to confirm the
disabling.
Silence will silence the alarm devices until a new alarm re-activates
them.
Disable will silence and disable the alarm devices, preventing them from
activating until they are enabled.
If the alarm devices at the panel have been silenced (e.g., by having
used the Silence command as shown in the example in Figure 9-14, or
by a user silencing the alarm devices at the remote panel or a connected
Remote FBP) Activated FBP-Silenced will be displayed on the fourth
line and the F1 command will be RESOUND as shown in the example in
Figure 9.15.
SID 2 Alarm Devices
|
Building E
|
PREV
|
NEXT
Activated |
DISABLE
SILENCE
SID 1 Alarm Devices
|
Gate House
|
PREV
|
NEXT
|
DISABLE