Event ID Description
ZInfo1 : Periphery address
ZInfo2 : Slot
0xE017 Error at access to integrated slave
0xE018 Error at mapping of the master periphery
0xE019 Error at standard back plane bus system recognition
0xE01A Error at recognition of the operating mode (8 / 9 bit)
0xE01B Error - maximum number of plug-in modules exceeded
0xE020 Error - Interrupt information undefined
ZInfo2 : Slot
ZInfo3 : Not relevant to the user
DatID : Interrupt type
0xE030 Error of the standard bus
0xE033 Internal error - Please contact the hotline!
0xE0B0 SPEED7 is not stoppable (e.g. undefined BCD value at timer)
ZInfo1 : Not relevant to the user
ZInfo2 : Not relevant to the user
ZInfo3 : Not relevant to the user
DatID : Not relevant to the user
0xE0C0 Not enough space in work memory for storing code block (block size exceeded)
0xE0CB Error at SSL access
ZInfo1 : Error
4: SSL wrong
5: Sub-SSL wrong
6: Index wrong
ZInfo2 : SSL ID
ZInfo3 : Index
0xE0CC Communication errors
ZInfo1 : Error code
1: Wrong priority
2: Buffer overflow
3: Telegram format error
4: Wrong SSL request (SSL ID not valid)
5: Wrong SSL request (SSL sub ID invalid)
6: Wrong SSL request (SSL-Index not valid)
7: Wrong value
8: Wrong return value
9: Wrong SAP
10: Wrong connection type
VIPA System 300SDeployment CPU 314-6CF03
Diagnostic entries
HB140 | CPU | 314-6CF03 | GB | 16-43 96