V 810 Chapter 5 Checking and removing errors
83
1: P9.01 is set improperly.
2: The load is too high or
another motor is connected to
the motor.
3: The AC inverter model is of
too small power class.
1: Set P9.01 correctly.
2: Reduce the load and check
the motor and the mechanical
condition.
3: Select an inverter of higher
power class.
1: The three-phase power
supply is faulty
2: The inverter motherboard is
faulty.
3: The inverter's optical board
is defective.
4: The control panel main
board is faulty.
1: Troubleshoot the power
supply
2: Look for technical support
3: Look for technical support
4: Look for technical support
1: The cable connecting the AC
drive and the motor is faulty.
2: The AC inverter's three-
phase output is unbalanced
when the motor is running.
3: The inverter board is faulty.
4: The module is faulty.
1: Eliminate external faults.
2: Check whether the motor
three-phase winding is
normal.
3: Find technical support
4. Find technical support
1: The ambient temperature is
too high.
2: The air filter is blocked.
3: The fan is damaged.
4: The thermally sensitive
resistor of the module is
defective.
5: The inverter module is
defective.
1: Lower the ambient High.
2: Clean the air filter.
3: Replace the defective fen
4: Replace the defective
thermally sensitive resistor.
5: Replace the inverter
module.