6 Digital Set Point
7 Differential Set Point
8 Digital Ratio
9 Remote 2
10 Remote 3
11 Alternate Control
12 Manual Control
13 Reverse Outputs
14 Activate Messages
15 Lock Auto/Man
1066 Function, Digital Input 4
r/w 0 Off
1 Panel Lock
2 Reset Alarm 1
3 Reset Alarm 2
4 Reset Both Alarms
5 Control Outputs Off
6 Digital Set Point
7 Differential Set Point
8 Digital Ratio
9 Remote 2
10 Remote 3
11 Alternate Control
12 Manual Control
13 Reverse Outputs
14 Activate Messages
15 Lock Auto/Man
714 High Power Limit, Control Output 1A
r/w Low Limit+1 to 100%
731 High Power Limit, Control Output 1B
r/w Low Limit+1 to 100%
711 High Scale, Retransmit Output 1
r/w -19999 to 30000 (maximum sensor range)
728 High Scale, Retransmit Output 2
r/w -19999 to 30000 (maximum sensor range)
2607 Hysteresis 1A, Cascade PID Set 1
r/w 1 to 30000
2627 Hysteresis 1A, Cascade PID Set 2
r/w 1 to 30000
2647 Hysteresis 1A, Cascade PID Set 3
r/w 1 to 30000
2667 Hysteresis 1A, Cascade PID Set 4
r/w 1 to 30000
2687 Hysteresis 1A, Cascade PID Set 5
r/w 1 to 30000
507 Hysteresis 1A, PID Set 1
r/w 1 to 30000
517 Hysteresis 1A, PID Set 2
r/w 1 to 30000
527 Hysteresis 1A, PID Set 3
r/w 1 to 30000
537 Hysteresis 1A, PID Set 4
r/w 1 to 30000
547 Hysteresis 1A, PID Set 5
r/w 1 to 30000
2617 Hysteresis 1B, Cascade PID Set 1
r/w 1 to 30000
2637 Hysteresis 1B, Cascade PID Set 2
r/w 1 to 30000
2657 Hysteresis 1B, Cascade PID Set 3
r/w 1 to 30000
2677 Hysteresis 1B, Cascade PID Set 4
r/w 1 to 30000
2697 Hysteresis 1B, Cascade PID Set 5
r/w 1 to 30000
557 Hysteresis 1B, PID Set 1
r/w 1 to 30000
567 Hysteresis 1B, PID Set 2
r/w 1 to 30000
577 Hysteresis 1B, PID Set 3
r/w 1 to 30000
587 Hysteresis 1B, PID Set 4
r/w 1 to 30000
597 Hysteresis 1B, PID Set 5
r/w 1 to 30000
1504 Input 1 AtoD, Diagnostic
r HHHH
101 Input 1 Error, Status
r0None
1 AtoD Under Flow
2 Sensor Under Range
3 Sensor Over Range
4 AtoD Over Flow
5 AtoD Timeout
6 Open Loop
903 Input 1 Failure, System
r/w 0% to High Power Limit (heat only or cool only)
Cool High Power Limit to Heat High Power Limit
(heat/cool or cool/heat)
210 Input 1 Open Loop, Status
r (0) Off, (1) On
100 Input 1 Value, Status
rxx
8 Input 1, Diagnostic
r0None
8 Univ
1505 Input 2 AtoD, Diagnostic
r HHHH
9 Input 2, Diagnostic
r0None
8 Univ
1506 Input 3 AtoD, Diagnostic
r HHHH
10 Input 3, Diagnostic
r Univ
2601 Integral 1A, Cascade PID Set 1
r/w 0 to 9999 minutes in hundredths
2621 Integral 1A, Cascade PID Set 2
r/w 0 to 9999 minutes in hundredths
2641 Integral 1A, Cascade PID Set 3
r/w 0 to 9999 minutes in hundredths
2661 Integral 1A, Cascade PID Set 4
r/w 0 to 9999 minutes in hundredths
2681 Integral 1A, Cascade PID Set 5
r/w 0 to 9999 minutes in hundredths
501 Integral 1A, PID Set 1
r/w 0 to 9999 minutes in hundredths
511 Integral 1A, PID Set 2
r/w 0 to 9999 minutes in hundredths
521 Integral 1A, PID Set 3
r/w 0 to 9999 minutes in hundredths
531 Integral 1A, PID Set 4
r/w 0 to 9999 minutes in hundredths
541 Integral 1A, PID Set 5
r/w 0 to 9999 minutes in hundredths
2611 Integral 1B, Cascade PID Set 1
r/w 0 to 9999 minutes in hundredths
2631 Integral 1B, Cascade PID Set 2
r/w 0 to 9999 minutes in hundredths
2651 Integral 1B, Cascade PID Set 3
r/w 0 to 9999 minutes in hundredths
2671 Integral 1B, Cascade PID Set 4
r/w 0 to 9999 minutes in hundredths
2691 Integral 1B, Cascade PID Set 5
r/w 0 to 9999 minutes in hundredths
551 Integral 1B, PID Set 1
r/w 0 to 9999 minutes in hundredths
561 Integral 1B, PID Set 2
r/w 0 to 9999 minutes in hundredths
571 Integral 1B, PID Set 3
r/w 0 to 9999 minutes in hundredths
9.6 Communications Watlow Series F4P