Watlow Series F4P Communications ■ 9.5
503 Derivative 1A, PID Set 1
r/w 0 to 999 minutes (in hundredths)
513 Derivative 1A, PID Set 2
r/w 0 to 999 minutes (in hundredths)
523 Derivative 1A, PID Set 3
r/w 0 to 999 minutes (in hundredths)
533 Derivative 1A, PID Set 4
r/w 0 to 999 minutes (in hundredths)
543 Derivative 1A, PID Set 5
r/w 0 to 999 minutes (in hundredths)
2613 Derivative 1B, Cascade PID Set 1
r/w 0 to 999 minutes (in hundredths)
2633 Derivative 1B, Cascade PID Set 2
r/w 0 to 999 minutes (in hundredths)
2653 Derivative 1B, Cascade PID Set 3
r/w 0 to 999 minutes (in hundredths)
2673 Derivative 1B, Cascade PID Set 4
r/w 0 to 999 minutes (in hundredths)
2693 Derivative 1B, Cascade PID Set 5
r/w 0 to 999 minutes (in hundredths)
553 Derivative 1B, PID Set 1
r/w 0 to 999 minutes (in hundredths)
563 Derivative 1B, PID Set 2
r/w 0 to 999 minutes (in hundredths)
573 Derivative 1B, PID Set 3
r/w 0 to 999 minutes (in hundredths)
583 Derivative 1B, PID Set 4
r/w 0 to 999 minutes (in hundredths)
593 Derivative 1B, PID Set 5
r/w 0 to 999 minutes (in hundredths)
314 Digital Differential Set Point 1, Control Set Points
r/w -19999 to 30000
333 Digital Differential Set Point 2, Control Set Points
r/w -19999 to 30000
352 Digital Differential Set Point 3, Control Set Points
r/w -19999 to 30000
371 Digital Differential Set Point 4, Control Set Points
r/w -19999 to 30000
201 Digital Input 1, Status
r0Low
1 High
213 Digital Input 2, Status
r0Low
1 High
225 Digital Input 3, Status
r0Low
1 High
237 Digital Input 4, Status
r0Low
1 High
315 Digital Ratio Set Point 1, Control Set Points
r/w 0% to 30000%
334 Digital Ratio Set Point 2, Control Set Points
r/w 0% to 30000%
353 Digital Ratio Set Point 3, Control Set Points
r/w 0% to 30000%
372 Digital Ratio Set Point 4, Control Set Points
r/w 0% to 30000%
308 Digital Set Point 1, Control Set Points
r/w Set Point Low Limit to Set Point High Limit
327 Digital Set Point 2, Control Set Points
r/w Set Point Low Limit to Set Point High Limit
346 Digital Set Point 3
r/w Set Point Low Limit to Set Point High Limit
365 Digital Set Point 4, Control Set Points
r/w Set Point Low Limit to Set Point High Limit
1513 Display Test, Test
w1Perform Display Test
844 Duplex Output, Control Output 1A
r/w 0 Off
1On
607 Error Latch, Analog Input 1
r/w 0 Self Clear
1 Latch
617 Error Latch, Analog Input 2
r/w 0 Self Clear
1 Latch
627 Error Latch, Analog Input 3
r/w 0 Self Clear
1 Latch
1303 Factory Page, Set Lockout
r/w 0 Full Access
1 Read Only
2 Password
880 Failure Mode, System
r/w 0 Bumpless Transfer
1 Fixed
604 Filter Time, Analog Input 1
r/w -60.0 to 60.0
614 Filter Time, Analog Input 2
r/w -60.0 to 60.0
624 Filter Time, Analog Input 3
r/w -60.0 to 60.0
1602 Full Defaults, Test
w0yes
700 Function, Control Output 1A
r/w 0 Off
1 Heat [reverse]
2 Cool [direct]
717 Function, Control Output 1B
r/w 0 Off
1 Heat [reverse]
2 Cool [direct]
1060 Function, Digital Input 1
r/w 0 Off
1 Panel Lock
2 Reset Alarm 1
3 Reset Alarm 2
4 Reset Both Alarms
5 Control Outputs Off
6 Digital Set Point
7 Differential Set Point
8 Digital Ratio
9 Remote 2
10 Remote 3
11 Alternate Control
12 Manual Control
13 Reverse Outputs
14 Activate Messages
15 Lock Auto/Man
1062 Function, Digital Input 2
r/w 0 Off
1 Panel Lock
2 Reset Alarm 1
3 Reset Alarm 2
4 Reset Both Alarms
5 Control Outputs Off
6 Digital Set Point
7 Differential Set Point
8 Digital Ratio
9 Remote 2
10 Remote 3
11 Alternate Control
12 Manual Control
13 Reverse Outputs
14 Activate Messages
15 Lock Auto/Man
1064 Function, Digital Input 3
r/w 0 Off
1 Panel Lock
2 Reset Alarm 1
3 Reset Alarm 2
4 Reset Both Alarms
5 Control Outputs Off
✔