Watlow Series F4P Parameters ■ 6.31
✔ Note: For more information about how parameter settings affect the
controller’s operation, see the Features Chapter.
Factory Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1601
write only
—
Input 1 (0)
Input 2 (1)
Input 3 (2)
Restore Input x (1 to 3)
Calibration
Restores original factory
calibration
values.
Main > Factory > Calibration > Restore Input x (1 to 3) Calibration
Restore Input x (1 to 3) Calibration
Active: Always.
Output
1607 [1A]
1612 [1B]
Rexmit
1627 [1]
1632 [2]
r/w
10.000V0.000 to 12.000V
(0 to 12000)
10.000V
Store 10.000V calibration
for process output.
Active: Always.
Output
1606 [1A]
1611 [1B]
Rexmit
1626 [1]
1631 [2]
r/w
1.000V0.000 to 3.000V
(0 to 3000)
1.000V
Store 1.000V calibration
for the process output.