901 °F or °C, System
r/w 0 °F
1°C
103 % Power Output 1A, Status
rValue
107 % Power Output 1B, Status
rValue
3050 Activate Message, Digital Input 1
r/w 0 Message 1
1 Message 2
2 Message 3
3 Message 4
3051 Activate Message, Digital Input 2
r/w 0 Message 1
1 Message 2
2 Message 3
3 Message 4
3052 Activate Message, Digital Input 3
r/w 0 Message 1
1 Message 2
2 Message 3
3 Message 4
3053 Activate Message, Digital Input 4
r/w 0 Message 1
1 Message 2
2 Message 3
3 Message 4
303 Alarm 1 High Deviation, Alarm Set Points
r/w 1 to 30000
303 Alarm 1 High Set Point, Alarm Set Points
r/w <per sensor> to Alarm 1 Low Set Point
303 Alarm 1 Maximum High Rate, Alarm Set Points
r/w Alarm 1 Low Maximum Rate +1 to 30000
302 Alarm 1 Low Deviation, Alarm Set Points
r/w -19999 to -1
302 Alarm 1 Low Set Point, Alarm Set Points
r/w <per sensor> to Alarm 1 High Set Point
302 Alarm 1 Maximum Low Rate, Alarm Set Points
r/w -19999 to Alarm 1 Maximum Rate High -1
102 Alarm 1, Status
r0Off
1 Alarm High
2 Alarm Low
322 Alarm 2 High Deviation, Alarm Set Points
r/w 1 to 30000
322 Alarm 2 High Set Point, Alarm Set Points
r/w <per sensor> to Alarm 2 Low Set Point
322 Alarm 2 Maximum High Rate, Alarm Set Points
r/w Alarm 2 Low Maximum Rate +1 to 30000
321 Alarm 2 Low Deviation, Alarm Set Points
r/w -9999 to -1
321 Alarm 2 Low Set Point, Alarm Set Points
r/w <per sensor> to Alarm 2 High Set Point
321 Alarm 2 Maximum Low Rate, Alarm Set Points
r/w -19999 to Alarm 2 Maximum Rate High -1
106 Alarm 2, Status
r0Off
1 Alarm High
2 Alarm Low
703 Alarm Hysteresis, Alarm Output 1
r/w 1 to 9999
720 Alarm Hysteresis, Alarm Output 2
r/w 1 to 9999
707 Alarm Logic, Alarm Output 1
r/w 0 Open on Alarm
1 Close on Alarm
724 Alarm Logic, Alarm Output 2
r/w 0 Open on Alarm
1 Close on Alarm
708 Alarm Messages, Alarm Output 1
r/w 0 Yes on Main Page
1No
725 Alarm Messages, Alarm Output 2
r/w 0 Yes on Main Page
1No
706 Alarm Sides, Alarm Output 1
r/w 0 Both
1 Low
2 High
723 Alarm Sides, Alarm Output 2
r/w 0 Both
1 Low
2 High
716 Alarm Source, Alarm Output 1
r/w 0 Input 1
1 Input 2
2 Input 3
733 Alarm Source, Alarm Output 2
r/w 0 Input 1
1 Input 2
2 Input 3
702 Alarm Type, Alarm Output 1
r/w 0 Off
1Process
2 Deviation
3 Maximum Rate
719 Alarm Type, Alarm Output 2
r/w 0 Off
1Process
2 Deviation
3 Maximum Rate
836 Analog Range, Retransmit Output 1
r/w 0 4 to 20mA
10 to 20mA
20 to 5V
31 to 5V
40 to 10V
837 Analog Range, Retransmit Output 2
r/w 0 4 to 20mA
10 to 20mA
20 to 5V
31 to 5V
40 to 10V
200 Auto/Manual Mode, Status
r/w 1 Auto Mode
2 Manual
1915 Auto/Manual Slidewire Calibration, Analog Input 3 r/w
r/w 0 Skip Calibration
1 Automatic
2 Manual
305 Autotune PID
r/w 0 Tune Off
9.2 ■ Communications Watlow Series F4P
Series F4P Modbus Registers
Parameters Sorted Alphabetically
A list of all Modbus registers in numerical order follows this alphabetical list. Register numbers listed are
relative. Add 40001 to convert to absolute addesses. For more information about parameters, see the Index.