Watlow PM LEGACY™ Limit Controller 66 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
USr.S
USr.S
Global
Save Settings As
Save all of this con-
troller's settings to
the selected set.
SEt1 User Set 1
(101)
SEt2 User Set 2
(102)
nonE None (61)
None
Instance 1
Map 1Map 2
26 26
0x(101)
1
0xE (14)
118 1014 uint
RWE
USr.r
USr.r
Global
Restore Settings
From
Replace all of this
controller's settings
with another set.
FCty Factory (31)
nonE None (61)
SEt1 User Set 1
(101)
SEt2 User Set 2
(102)
None
Instance 1
Map 1Map 2
24 24
0x65
(101)
1
0xD (13)
117 1013 uint
RWE
CoЛЏ
SEt
Communications Menu
PCoL
PCoL
Communications 1
Protocol
Set the protocol of this
controller to the proto-
col that this network is
using.
Std Standard Bus
(1286)
ЛЏod Modbus
RTU (1057)
Modbus Instance 1
Map 1Map 2
2492 2972
0x96
(150)
1
7
- - - - 17009 uint
RWE
Standard Bus
Ad.S
Ad.S
Communications 1
Standard Bus Ad-
dress
Set the network ad-
dress of this controller.
Each device on the
network must have a
unique address.
The Zone Display on
the front panel will dis-
play this number.
1 to 16 1 Instance 1
Map 1Map 2
2480 2960
0x96
(150)
1
1
- - - - 17001 uint
RWE
Modbus RTU
Ad.ЛЏ
Ad.M
Communications (1
or 2)
Modbus Address
Set the network ad-
dress of this controller.
Each device on the
network must have a
unique address.
1 to 247 1 Instance 1
Map 1Map 2
2482 2962
Instance 2
Map 1Map 2
2500 2980
0x96
(150)
1 to 2
2
- - - - 17007 uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set