Watlow PM LEGACY™ Limit Controller 67 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
bAUd
bAUd
Communications (1
or 2)
Baud Rate
Set the speed of this
controller's communi-
cations to match the
speed of the
Modbus
serial network.
9600 9,600 (188)
19.2 19,200 (189)
38.4 38,400 (190)
9,600 Instance 1
Map 1Map 2
2484 2964
Instance 2
Map 1 Map 2
2504 2984
0x96
(150)
1 to 2
3
- - - - 17002 uint
RWE
PAr
PAr
Communications (1
or 2)
Parity
Set the parity of this
controller to match the
parity of the
Modbus
serial network.
nonE None (61)
EuEn Even (191)
odd Odd (192)
None Instance 1
Map 1Map 2
2486 2966
Instance 2
Map 1 Map 2
2506 2986
0x96
(150)
1 to 2
4
- - - - 17003 uint
RWE
C_f
C_F
Communications (1
or 2)
Display Units
Select whether this
communications chan-
nel will display in Cel-
sius or Fahrenheit.
f Fahrenheit (30)
C Celsius (15)
Note:
Applies to
Modbus and
Ethernet.
F Instance 1
Map 1Map 2
2490 2970
0x96
(150)
1
6
- - - - 17050 uint
RWE
ЛЏ.hL
M.hL
Communications (1
or 2)
Modbus Word Order
Select the word or-
der of the two 16-bit
words in the float-
ing-point values.
Lohi Low-High
(1331)
hiLo High-Low
(1330)
Low-High Instance 1
Map 1Map 2
2488 2968
Instance 2
Map 1 Map 2
2508 2988
0x96
(150)
1 to 2
5
- - - - 17043 uint
RWE
ЛЏap
Map
Communications (1
or 2)
Data Map
If set to 1 the control
will use PM legacy
mapping. If set to 2
the control will use
new mapping to ac-
commodate new func-
tions.
1 to 2 1 if 9
th
digit
of part
number
is a D or
1 other-
wise, 2.
- - - - - - - - - - - - 17059 uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set