Watlow PM LEGACY™ Limit Controller 69 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
C_F
C_F
Communications (2)
Display Units
Select which scale to
use for temperature
passed over commu-
nications port 2.
F °F (30)
C °C (15)
°F Instance 2
Map 1Map 2
- - - - 2990
0x96
(150)
2
6
199 17050 uint
RWE
nU.S
nU.S
Communications (2)
Non-volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM. The EEPROM
allows for approx-
imately one million
writes.
yEs Yes (106)
no No (59)
No Instance 2
Map 1Map 2
2514 2994
96 (150)
2
8
198 17051 uint
RWE
Profibus DP
P.Add
P.Add
Communications (2)
Profibus Node Ad-
dress
Set the Profibus ad-
dress for this control.
0 to 126
126 - - - - - - - - - - - - 17060 - - - -
a.Loc
A.Loc
Communications (2)
Profibus Address
Lock
When set to yes will
not allow address to
be changed using
software. Can be
changed from front
panel.
no No (59)
yES Yes (106)
No - - - - - - - - - - - - 17061 - - - -
stat
Stat
Communications
Profibus DP Status
Current Profibus sta-
tus.
rEdy Ready
(1662)
rng Running
(149)
- - - -
- - - - - - - - - - - - 17062 uint
R
C_F
C_F
Communications (2)
Display Units
Select which scale to
use for temperature
passed over commu-
nications port 2.
F °F (30)
C °C (15)
°F Instance 2
Map 1Map 2
- - - - 2990
0x96
(150)
2
6
199 17050 uint
RWE
** R: Read, W: Write, E: EEPROM, S: User Set