Watlow PM LEGACY™ Limit Controller 70 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
nU.S
nU.S
Communications (2)
Non-volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM. The EEPROM
allows for approx-
imately one million
writes.
yEs Yes (106)
no No (59)
No Instance 2
Map 1Map 2
2514 2994
96 (150)
2
8
198 17051 uint
RWE
Modbus TCP or EtherNet/IP
ЛЏ.hL
M.hL
Communications (2)
Modbus Word Order
Select the word or-
der of the two 16-bit
words in the float-
ing-point values.
Lohi Low-High
(1331)
hiLo High-Low
(1330)
Low-High Instance 1
Map 1Map 2
2488 2968
Instance 2
Map 1Map 2
2508 2988
0x96
(150)
1 to 2
5
- - - - 17043 uint
RWE
iP.ЛЏ
iP.M
Communications (2)
IP Address Mode
Select DHCP to let a
DHCP server assign
an address to this
module.
dhCP DHCP
(1281)
F.Add Fixed Ad-
dress (1284)
DHCP - - - - - - - - - - - - 17012 - - - -
Note:
When changing IP address, the control power must be cycled for the new address to take effect.
iP.F1
ip.F1
Communications (2)
IP Fixed Address Part
1
Set the IP address
of this module. Each
device on the network
must have a unique
address.
0 to 255 169 - - - - - - - - - - - - 17014 - - - -
iP.F2
ip.F2
Communications (2)
IP Fixed Address Part
2
Set the IP address
of this module. Each
device on the network
must have a unique
address.
0 to 255 254 - - - - - - - - - - - - 17015 - - - -
** R: Read, W: Write, E: EEPROM, S: User Set