Technical Specications
8
8-2 | CFW-11
Table 8.1 - Technical specications of the CFW-11 inverter series frame sizes F, G and H models at rated switching
frequencies
Model
CFW11
0242 T 4
CFW11
0312 T 4
CFW11
0370 T 4
CFW11
0477 T 4
CFW11
0515 T 4
CFW11
0601 T 4
CFW11
0720 T 4
CFW11
0760 T 4
CFW11
0795 T 4
CFW11
0877 T 4
CFW11
1062 T 4
CFW11
1141 T 4
Frame Size F G H
Number of Power Phases 3Φ
Use with Normal Duty
(ND) Cycle
Rated Output Current
(1)
242 312 370 477 515 601 720 760 795 877 1062 1141
Overload
Current
(2)
[Arms]
1 min 266 343 407 525 567 662 792 836 875 965 1168 1255
3 s 363 468 555 716 773 900 1080 1140 1193 1316 1593 1712
Rated Switching Frequency [kHz] 2 2 2 2 2 2 2 2 2 2 2 2
Maximum Motor
(3)
[HP/kW] 200/150 250/185 300/220 400/300 400/300 500/370 600/440 650/480 700/515 750/560 950/700 1000/750
Rated Input Current 242 312 370 477 515 601 720 760 795 877 1062 1141
Dissipated
Power [W]
Surface
Mounting
(4)
2651 3957 4578 6059 6490 7044 8532 10055 9851 10993 12498 13558
Flange
Mounting
(5)
622 826 900 1227 1339 1584 1685 2008 755 759 764 768
Use with Heavy Duty
(HD) Cycle
Rated Output Current
(1)
211 242 312 370 477 515 560 600 637 715 855 943
Overload
Current
(2)
[Arms]
1 min 317 363 468 555 716 773 840 900 956 1073 1283 1415
3 s 422 484 624 740 954 1030 1120 1200 1274 1430 1710 1886
Rated Switching Frequency [kHz] 2 2 2 2 2 2 2 2 2 2 2 2
Maximum Motor
(3)
[HP/kW] 175/132 200/150 250/185 300/220 400/300 400/300 450/330 500/370 550/400 600/440 750/560 800/590
Rated Input Current [Arms] 211 242 312 370 477 515 560 600 637 715 855 943
Dissipated
Power [W]
Surface
Mounting
(4)
2296 3046 3829 4669 6005 6005 6589 7909 7824 8836 9916 11022
Flange
Mounting
(5)
524 614 722 915 1232 1320 1253 1550 747 751 753 757
Surrounding Air Temperature [ºC (ºF)]
-10...45 ºC
(14...113 ºF)
-10...40 ºC
(14...104 ºF)
RFI Filter Built-in
Weight [kg (lb)] 130 132 135 140 204 207 215 215 213 213 220 220
Availability of Option Kits
that can be Integrated
into the Product (refer
to the smart code in the
Section 2.5 HOW TO
SPECIFY THE CFW-11
MODEL (SMART CODE)
on page 2-14)
Safety Stop Yes
24 Vdc External Control Power
Supply
Yes