EasyManua.ls Logo

WEG CFW-11 - Page 43

WEG CFW-11
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Connection
3
CFW-11 | 3-17
Model
Frame size
Power terminals
Duty
cycle
Wiring
Fuse
[A]
Fuse I2t
@ 25 ºC
Terminals
[A2s]
Terminals
Bolt
(wrench/bolt
head type)
Recommended
torque N.m
(lbf.in)
mm
2
AWG Terminais
CFW110795T4DC
H
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD 3 x 150 3 x 300
Ring
tongue
2 x
640
See
note
(2)
ND 3 x 185 3 x 400
DC+, DC-
M12 (Phillips
hex head)
60 (531.00) HD/ND 4 in
(1)
102 mm
(1)
M8 (Phillips
hex head)
10 (88.5) HD/ND 185 400
CFW110877T4DC
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD 4 x 120 4 x 4/0
Ring
tongue
2 x
830
See
note
(2)
ND 4 x 150 4 x 300
DC+, DC-
M12 (Phillips
hex head)
60 (531.00) HD/ND 2 x 3 in
(1)
2 x 76mm
(1)
M8 (Phillips
hex head)
10 (88.5) HD/ND 4 x 120 4 x 4/0
CFW111062T4DC
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD 4 x 150 4 x 300
Ring
tongue
2 x
890
See
note
(2)
ND 4 x 240 4 x 500
DC+, DC-
M12 (Phillips
hex head)
60 (531.00) HD/ND 2 x 3 in
(1)
2 x 76mm
(1)
M8 (Phillips
hex head)
10 (88.5) HD/ND 2 x 120 2 x 410
CFW111141T4DC
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60 (531.00)
HD 2 x 120 2 x 4/0
Ring
tongue
2 x
1035
See
note
(2)
ND 4 x 185 4 x 350
DC+, DC-
M12 (Phillips
hex head)
60 (531.00) HD/ND 2 x 4 in
(1)
2 x 102mm
(1)
M8 (Phillips
hex head)
10 (88.5) HD/ND 2 x 150 2 x 300
(1) 1/4-in (6.4mm) copper bus bar must be used with width specified in Table 3.3 on page 3-16.
(2) Use fuses with I
2
t value smaller than or equal to the value specified in Table 3.2 on page 3-13 and voltage and breaking capacity for 800 Vdc.

Table of Contents

Other manuals for WEG CFW-11

Related product manuals