Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014 Page 146
Output 5 Parameters
Parameter Name & Register Address
Integer Int +1 Float Access Values & Descriptions
Linear Output 5 Fitted Value Linear Output 5 Fitted
Dec 3005 19389 38778
RO
0 Not fitted
Hex 0BBD 4BBD 977A
1 Fitted
Output 5 Usage Value Output 5 Function
Dec 10106 26490 52980
RW
0 Disabled
Hex 277A 677A CEF4
1 Loop 1 Primary Output Power
2 Loop 1 Secondary Output Power
3 Loop 1 VMD Open
4 Loop 1 VMD Close
5 Loop 2 Primary Output Power
6 Loop 2 Secondary Output Power
7 Loop 2 VMD Open
8 Loop 2 VMD Close
9 OR Alarm Event Direct
10 OR Alarm Event Reverse
11 AND Alarm Event Direct
12 AND Alarm Event Reverse
Output 5 Status Value Output 5 Status
Dec 3006 19390 38780
RO
0 Inactive
Hex 0BBE 4BBE 977C
1 Active
Digital Output 5 Latch Enable Value Latch Enable
Dec 3007 19391 38782
RW
0 Disable
Hex 0BBF 4BBF 977E
1 Enable
Digital Output 5 Clear Latch Value Latch Clear
Dec 3009 19393 38786
RW
0 Do Nothing
Hex 0BC1 4BC1 9782
1 Clear Latch
Digital Output 5 Latch State Value Latch State
Dec 3008 19392 38784
RO
0 Unlatched
Hex 0BC0 4BC0 9780
1 Latched
Output 5 OR Alarm Selection Bit If Bit = 1, Alarm n Is Included in OR Selection
Dec 10131 26515 53030
RW
2 Alarm 1
Hex 2793 6793 CF26
3 Alarm 2
4 Alarm 3
5 Alarm 4
6 Alarm 5
7 Alarm 6
8 Alarm 7
Output 5 OR Event Selection Bit If Bit = 1, Event n Is Included in OR Selection
Dec 10132 26516 53032
RW
2 Event 1
Hex 2794 6794 CF28
3 Event 2
4 Event 3
5 Event 4
6 Event 5
7 Profile Running
8 Profile End