Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 65
NetComm Dropouts
• The number of lost or corrupted network communications tolerated by the
receiving unit.
• Excess numbers of NetComm Dropouts on network due to faulty wiring,
improper shielding, or improper setup will result in the unit experiencing the
dropouts to flash intermittently in the Sequencing Menu of the EGCP-2.
Typically set at 5 to 10 dropouts.
Unit Calibrated (true/false)
• When set for true, indicates unit has been factory calibrated. Requires Level
4 Security code to change.