11.4 Faults that are not displayed
Table 38 Faults that are not shown on the display
Appliance faults Remedy
Combustion noises too loud; rumbling noises Check the gas type.
Check the gas supply pressure.
Check the flue system; clean or repair if required.
Check the gas/air ratio.
Check the ratio control valve; replace if required.
Check condense drain is clear.
Check fan depression.
Flow noises Set the pump rate or pump characteristic map correctly and match to the maximum
output.
Heat-up takes too long. Set the pump rate or pump characteristic map correctly and match to the maximum
output.
Check system is balanced.
Check anti-cycle time.
Flue gas values incorrect; CO content too high. Check the gas type.
Check the gas supply pressure.
Check the flue system; clean or repair if required.
Check the gas/air ratio.
Check the ratio control valve; replace if required.
Delayed ignition, poor ignition. Check the ignition transformer function for misfiring in Menu 6, replace if required.
Check the gas type.
Check the gas supply pressure.
Check operation of meter governor.
Check the power supply.
Check the electrodes; replace if required.
Check the flue system; clean or repair if required.
Check the gas/air ratio.
Check the burner, replace if required.
Check the air/gas ratio control valve; replace if required.
Condensate in air box Check the non-return valve in the air/gas manifold, replace if required.
No hot water. Check the turbine, replace if required.
Check diverter valve
Check for cross-piping.
DHW volume is not reached. Check the plate heat exchanger.
Check flow device.
Check silencer body.
No function, the display remains dark. Check the electrical wiring for damage.
Replace defective cables.
Check the fuse, replace if required.

Table of Contents

Other manuals for Worcester GR2300iW C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GR2300iW C and is the answer not in the manual?

Worcester GR2300iW C Specifications

General IconGeneral
BrandWorcester
ModelGR2300iW C
CategoryBoiler
LanguageEnglish

Related product manuals