Possible Cause
Fault Code
Fault
Number
- High temperature of installation
environment
- High switching frequency
- Fan failure
- High load on the motor
- Proximity to the source of heat
- The fan and the heat sink of the
device being dirty

Over Temperature
13
Check the ambient temperature. (Must be under 45)
Reduce the switching frequency as much as possible.
Clean the device heat sink with compressed air.
- The environment being too much
cold
- Disconnection of heat sensor

Under Temperature
14
If the air temperature is above -10 ° C, send the device
for repair.
- Low power of the device in
comparison with the required power

Output Power
15
Contact the company for a larger device.
- Low power of the brake resistance
for the desired application

Brake Resistor Over Load
16
Brake resistance with higher power is needed.
- Fault in the memory of the device
parameters

Emergency Fault
17
Contact the company.
- When a fault occurs in the device
software.

Hard Drive Fault
18
At this time, the device must be disconnected from
the circuit and sent to the company for service.
- Enable command is received earlier
than the contactor.

Early Enable
19
Check the control circuit and motor contactor and
reset the fault.
- Enable command is disconnected
while being sent.

Contactor Fault
24
Check the control circuit and motor contactor and
reset the fault.
- The motor is small.

Small Motor Fault
25
This fault will be displayed if a low-capacity motor is
connected to the inverter or the motor is