p = p
set
+ (k–1) * (P505 ACT.VAL.INC - P510 ACT.VAL.DEC)
P505 ACT.VAL.INC = P510 ACT.VAL.DEC Pressure constant, independent of how
many pumps are in operation.
P505 ACT.VAL.INC > P510 ACT.VAL.DECPressure rises when assist pump switches
on.
P505 ACT.VAL.INC < P510 ACT.VAL.DEC Pressure falls when assist pump switches
on.
To find out the right setting for Syncronous control
1. Start the first pump in P62 JOG mode.
2. Increase the frequency until the required value is met. Check the frequency at zero
consumption, f
0
.
3. Set the synchronous limit, f
0
+ 2..3 Hz.
4. Set the synchronous window between 1 or 2 Hz depending on the pump curve and the
set point.
11.5 Example: P900 SUBMENU OFFSET
General settings
Constant pressure system with the required value of 5 bar.
Additionally a flow sensor is connected to the offset input.
Parameter P907 OFFS.RANGE = 160 (maximum range of flow sensor = 16 m
3
/h).
System requirement 1
Constant pressure: 5 bar
Flow rate: 5 - 12 m
3
/h
Below 5 m
3
/h decrease the pressure to maximum 2,5 bar at a flow rate of 2 m
3
/h.
Settings:
Parameter P910 LEVEL 1 = 50 = 5 m
3
/h. First limit where the offset function is active.
Parameter P912 OFFSET X1 = 20 = 2 m
3
/h. Fixed point according to the requirements.
Parameter P913 OFFSET Y1 = 2,5 = 2,5 bar. Maximum allowed pressure at this flow
rate.
System requirement 2
Constant pressure: 5 bar
Flow rate: 5 - 12 m
3
/h
Above 12 m
3
/h increase the pressure with the limitation to have maximum 6,0 bar at
maximum flow rate of 16 m
3
/h.
Settings:
Parameter P915 LEVEL 2 = 120 = 120 m
3
/h. Second limit where the offset function is
active.
Parameter P917 OFFSET X2 = 160 = 16 m
3
/h. Fixed point according to the
requirements.
Parameter P918 OFFSET Y2 = 6 = 6 bar. Required pressure at this flow rate.
11 Technical Reference
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual 105

Table of Contents

Other manuals for Xylem hydrovar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem hydrovar and is the answer not in the manual?

Xylem hydrovar Specifications

General IconGeneral
Frequency50/60 Hz
Control typeVariable speed drive
Protection classIP55
Communication protocolsModbus
Relative Humidity5% - 95% (non-condensing)
AltitudeUp to 1000 m without derating
Input voltage200-690 V AC
Storage Temperature-25°C to +70°C (-13°F to 158°F)